ICX 500 Gateway
Doc.no.A100K12202
Page 9
ICX-500 requires configuration tool AlphaPro ver. 12 or higher
2.7. Factory Reset (Cold Boot)
The factory reset button is used to restore the ICX-500 to factory settings. The factory reset (cold
boot) button is located on rear side of the ICX-500, behind the same protection lid as the micro-
SD card.
Two different procedures are available:
Complete Factory Reset
:
•
Load default intercom database
•
Reset all IP settings to default (E.g., IP addresses and Filters). Eth0 will get IP address
169.254.1.5, subnet mask 255.255.0.0.
o
Press and hold the "Factory Default" button
o
Power up the ICX-500 while the button is pressed
o
Keep the button pressed for approx. 5 sec., then release it
•
T
his procedure will clear all settings done from the web interface
•
The procedure will also delete the License file, Log files, Audio
Messages (wav files), Audio Language Packages and Backup files
Factory Reset Intercom Configuration only:
•
Will Keep IP settings
•
Load default intercom database
o
Power up the ICX-500
o
Wait for 5 sec., then press and hold the “Factory Default” button
o
Keep the button pressed until the Status LED is flashing green or the fault relay is
clicking (Approx. 10 sec)
Factory reset can also be done from the ICX web interface: System Maintenance > System
Recovery > Load Factory Defaults