JOHNSON CONTROLS
FORM 145.05-NOM2 (807)
Point ID
Point Description
Variable
Type
Read ( R )
Write ( W )
Value
Range
(Analog
Only)
Unit
(Analog
Only)
Instance
Number
Comments
TUESDAYSCHED9
Turns Tuesday On / Off for
Schedule 9:
1= On - Active
0 = Off - Inactive
BBV
R/W
-
-
964
Unit Enable
Network Unit Start:
1 = Enable
0 = Disable
BBV
R/W
-
-
15001
Unsafe
External Safety Input Alarm:
1 = Fault
0 = No Fault
BBV
R
-
-
15103
VAV Fan En
VAV Fan Enable:
1 = VAV
0 = CV
BBV
R/W
-
-
15010
VFD Sp % by BAS
Communicated Supply Fan
VFD Speed
BAV
R
0 -100
%
16024
VFD Sp by BAS En
Enables the Use of a Supply
Fan VFD Communicated Input:
1 = Enabled
0 = Disabled
BBV
R/W
-
-
15013
VFDMod
Supply Fan VFD Speed
BAV
R
0 -100
%
16112
Only with VAV or
Flexsys
VLALOut
This is the Status of Binary
Value of the Output to the
Alarm Output:
1 = Alarm - Active
0 = No Alarm - Inactive
BBV
R
-
-
15610
VLB/P Mod
BAV
16803
Not Applicable
VLB/PMod
Status of the Analog Value
of the Output to the Bypass
Damper in %
BAV
R
16803
Only with Flexsys
Units
VLBoxOpn
Status of the Binary Value of
the VAV Boxes Output:
1 = Active
0 = Inactive
BBV
R
-
-
15605
VLC/WMod
BAV
-
-
16115
Not Applicable
VLCompA
BBV
-
-
15606
Not Applicable
VLCompB
BBV
-
-
15607
Not Applicable
VLCompC
BBV
-
-
15608
Not Applicable
VLCompD
BBV
-
-
15609
Not Applicable
VLCVEn
Status of the Binary Value of
the CV Fan Output:
1 = On - Active
0 = Off - Inactive
BBV
R
-
-
15601
VLE/Wmod
BAV
-
-
16804
Not Applicable
Continued on next page
TABLE 15 – BACnet MS/TP points (Cont.)
6
Summary of Contents for YSCD
Page 10: ...10 JOHNSON CONTROLS FORM 145 05 NOM2 807 THIS PAGE INTENTIONALLY LEFT BLANK ...
Page 12: ...12 JOHNSON CONTROLS FORM 145 05 NOM2 807 THIS PAGE INTENTIONALLY LEFT BLANK ...
Page 38: ...38 JOHNSON CONTROLS FORM 145 05 NOM2 807 THIS PAGE INTENTIONALLY LEFT BLANK ...
Page 46: ...46 JOHNSON CONTROLS FORM 145 05 NOM2 807 THIS PAGE INTENTIONALLY LEFT BLANK ...
Page 105: ...105 JOHNSON CONTROLS FORM 145 05 NOM2 807 LD13009 8 FIG 11 WIRING DIAGRAM POWER CIRCUIT ...