20
JOHNSON CONTROLS
FORM 145.05-NOM2 (807)
DATA
050
055
060
072
079
090
Capacity
Range
Min. capacity (tons)
40
50
55
65
70
80
Max. capacity (tons)
70
75
80
100
105
120
Airfl ow Range
Min. VAV design CFM
14,000
14,700
16,000
19,100
21,000
24,000
Max.VAV design & operating CFM
21,000
22,000
24,000
28,700
31,500
36,000
Cabinet
Dimensions
Depth (excluding return section)
84
70
84
84
96
96
Length
84
100
84
98
120
120
Height (excluding discharge plenum)
99
79
99
99
99
99
Box type
N1
M5
N1
N2
N3
N3
Cooling Coil
Section
Face Area
35
36.7
40
47.8
52.5
60.0
Heating
Section
Hot Water Heat–Face Area
35
36.7
40
47.8
52.5
60.0
Rows–10 FPI
1 or 2
1 or 2
1 or 2
1 or 2
1 or 2
1 or 2
Electric Heat–kW
TBD
TBD
TBD
TBD
TBD
TBD
Steam–Face Area
35
36.7
40
47.8
52.5
60
Rows–8 FPI
1
1
1
1
1
1
Return Air
Section
Filter Type
2” or 4” PLEATED, 12” CARTRIDGE
Filter area
40.8
36.7
40.8
48.9
62.5
62.5
Pre-fi lter
2” or 4
2” or 4
2” or 4
2” or 4
2” or 4
2” or 4
Effi ciency (%)
30 to 95
30 to 95
30 to 95
30 to 95
30 to 95
30 to 95
Final-Filter
4” or 12”
4” or 12”
4” or 12”
4” or 12”
4” or 12”
4” or 12”
Effi ciency (%)
65–95
65–95
65–95
65–95
65–95
65–95
Fan Section
Type
AIRFOIL PLENUM FAN (SWSI)
Quantity–Dia. (in): standard capacity
1–30
1–27
1–30
1-33
1-36
1-36
Quantity–Dia. (in): high capacity
1–33
n/a
1–33
1-36
1-40
1-40
Motor HP range
3.0–30.0
3.0–20.0
3.0–30.0
3.0-40.0
5.0-50.0
5.0-50.0
TABLE 6 – DATA TABLE (CONTINUED)
Due to the dedication of continuous product improvement and enhancements, the information provided is subject to change without notice.
* Aluminum fi ns standard. ** M-Available Modular Construction, N- for New Construction.
TABLE 7 – CHILLED WATER COIL PERFORMANCE
UNIT
SIZE
012
016
021
025
032
039
048
050
055
060
072
079
090
EAT
23,000 CFM 2 ROW COIL
DB/WB
78.5/64
EWT
44
TMBH
625
SMBH
515
LDB
58.4
LWB
55.0
GPM
125
EAT
25,000 CFM 3 ROW COIL
DB/WB
78.5/64
EWT
44
TMBH
625
SMBH
515
LDB
55.8
LWB
54.1
GPM
113
Installation
Summary of Contents for YSCD
Page 10: ...10 JOHNSON CONTROLS FORM 145 05 NOM2 807 THIS PAGE INTENTIONALLY LEFT BLANK ...
Page 12: ...12 JOHNSON CONTROLS FORM 145 05 NOM2 807 THIS PAGE INTENTIONALLY LEFT BLANK ...
Page 38: ...38 JOHNSON CONTROLS FORM 145 05 NOM2 807 THIS PAGE INTENTIONALLY LEFT BLANK ...
Page 46: ...46 JOHNSON CONTROLS FORM 145 05 NOM2 807 THIS PAGE INTENTIONALLY LEFT BLANK ...
Page 105: ...105 JOHNSON CONTROLS FORM 145 05 NOM2 807 LD13009 8 FIG 11 WIRING DIAGRAM POWER CIRCUIT ...