102
JOHNSON CONTROLS
FORM 145.05-NOM2 (807)
TABLE 23 – CONSTANT VOLUME / VARIABLE AIR VOLUME EXPANSION CONTROL BOARD *
BOARD
CONNECTOR
POINT
I/O TYPE
INPUT DEVICE
INPUT
IN-1
ANALOG INPUT
NOT USED
0-5 VDC
IN-2
ANALOG INPUT
NOT USED
0-5 VDC
IN-3
ANALOG INPUT
NOT USED
0-5 VDC
IN-4
ANALOG INPUT
NOT USED
0-5 VDC
IN-5
ANALOG INPUT
NOT USED
0-5 VDC
IN-6
ANALOG INPUT
NOT USED
0-5 VDC
IN-7
ANALOG INPUT
NOT USED
0-5 VDC
IN-8
ANALOG INPUT
NOT USED
0-5 VDC
IN-9
ANALOG INPUT
ENTERING WATER TEMP
THERMISTOR
IN-10
ANALOG INPUT
LEAVING WATER TEMP
THERMISTOR
IN-11
NOT USED
IN-12
BINARY INPUT
DIRTY FILTER SWITCH
DRY CONTACT 5 VDC VOLTAGE
IN-13
BINARY INPUT
FREEZESTAT
DRY CONTACT 5 VDC VOLTAGE
IN-14
BINARY INPUT
EXTERNAL SAFETY INPUT
DRY CONTACT 5 VDC VOLTAGE
IN-15
BINARY INPUT
SYSTEM ON INPUT
DRY CONTACT 5 VDC VOLTAGE
IN-16
BINARY INPUT
SYSTEM OFF INPUT
DRY CONTACT 5 VDC VOLTAGE
DO-1
BINARY OUTPUT
DRY CONTACT
DO-2
BINARY OUTPUT
DRY CONTACT
DO-3
BINARY OUTPUT
DRY CONTACT
DO-4
BINARY OUTPUT
DRY CONTACT
DO-5
NOT USED
DO-6
NOT USED
DO-7
BINARY OUTPUT
STAGE HEAT 2ND STAGE /TRI STATE HEAT OPEN
DRY CONTACT
DO-8
BINARY OUTPUT
STAGE HEAT 1ST STAGE / TRI STATE HEAT CLOSED
DRY CONTACT
* Check the wiring diagram in the unit for the exact location of the input and outputs as they may change based
on the confi guration of the unit.
Service
Summary of Contents for YSCD
Page 10: ...10 JOHNSON CONTROLS FORM 145 05 NOM2 807 THIS PAGE INTENTIONALLY LEFT BLANK ...
Page 12: ...12 JOHNSON CONTROLS FORM 145 05 NOM2 807 THIS PAGE INTENTIONALLY LEFT BLANK ...
Page 38: ...38 JOHNSON CONTROLS FORM 145 05 NOM2 807 THIS PAGE INTENTIONALLY LEFT BLANK ...
Page 46: ...46 JOHNSON CONTROLS FORM 145 05 NOM2 807 THIS PAGE INTENTIONALLY LEFT BLANK ...
Page 105: ...105 JOHNSON CONTROLS FORM 145 05 NOM2 807 LD13009 8 FIG 11 WIRING DIAGRAM POWER CIRCUIT ...