Point ID
Point Description
Variable
Type
Read ( R )
Write ( W )
Value
Range
(Analog
Only)
Unit
(Analog
Only)
Instance
Number
Comments
SCHEDULE4STAT
Gives the Status of Schedule 4:
1 = On - Active
0 = Off - Inactive
BBV
R
-
-
854
SCHEDULE5STAT
Gives the Status of Schedule 5:
1 = On - Active
0 = Off - Inactive
BBV
R
-
-
855
SCHEDULE6STAT
Gives the Status of Schedule 6:
1 = On - Active
0 = Off - Inactive
BBV
R
-
-
856
SCHEDULE7STAT
Gives the Status of Schedule 7:
1 = On - Active
0 = Off - Inactive
BBV
R
-
-
857
SCHEDULE8STAT
Gives the Status of Schedule 8:
1 = On - Active
0 = Off - Inactive
BBV
R
-
-
858
SCHEDULE9STAT
Gives the Status of Schedule 9:
1 = On - Active
0 = Off - Inactive
BBV
R
-
-
859
Side1
BAV
-
-
15115
Not Applicable
Side2
BAV
-
-
15114
Not Applicable
Slab Temp
Under Floor Slab Temperature
BAI
R
0 -120
Deg F
13020
Only with Flexsys
SQAcStg1%*
Cooling PID Output for 1ST
Stage Cooling Operation
BAV
R/W
0 -100
%
16201
SQAcStg2%*
Cooling PID Output for 2ND
Stage Cooling Operation
BAV
R/W
0 -100
%
16202
SQAcStg3%*
Cooling PID Output for 3RD
Stage Cooling Operation
BAV
R/W
0 -100
%
16203
SQAcStg4%*
Cooling PID Output for 4TH
Stage Cooling Operation
BAV
R/W
0 -100
%
16204
SQAcStg5%*
Cooling PID Output for 5TH
Stage Cooling Operation
BAV
R/W
0 -100
%
16205
SQAcStg6%*
Cooling PID Output for 6TH
Stage Cooling Operation
BAV
R/W
0 -100
%
16206
SQHtStg1%*
Heating PID Output for 1ST
Stage Operation
BAV
R/W
0 -100
%
16207
SQHtStg2%*
Heating PID Output for 2ND
Stage Operation
BAV
R/W
0 -100
%
16208
SQHtStg3%*
Heating PID Output for 3RD
Stage Operation
BAV
R/W
0 -100
%
16209
SQHtStg4%*
Heating PID Output for 4TH
Stage Operation
BAV
R/W
0 -100
%
16210
START HR1
Start Hours for Schedule 1
BAV
R/W
1- 24
-
870
START HR10
Start Hours for Schedule 10
BAV
R/W
1- 24
-
970
START HR11
Start Hours for Schedule 11
BAV
R/W
1- 24
-
981
Continued on next page
TABLE 15 – BACnet MS/TP points (Cont.)
User Interface Control Center
Summary of Contents for YSCD
Page 10: ...10 JOHNSON CONTROLS FORM 145 05 NOM2 807 THIS PAGE INTENTIONALLY LEFT BLANK ...
Page 12: ...12 JOHNSON CONTROLS FORM 145 05 NOM2 807 THIS PAGE INTENTIONALLY LEFT BLANK ...
Page 38: ...38 JOHNSON CONTROLS FORM 145 05 NOM2 807 THIS PAGE INTENTIONALLY LEFT BLANK ...
Page 46: ...46 JOHNSON CONTROLS FORM 145 05 NOM2 807 THIS PAGE INTENTIONALLY LEFT BLANK ...
Page 105: ...105 JOHNSON CONTROLS FORM 145 05 NOM2 807 LD13009 8 FIG 11 WIRING DIAGRAM POWER CIRCUIT ...