61
JOHNSON CONTROLS
FORM 145.05-NOM2 (807)
Point ID
Point Description
Variable
Type
Read ( R )
Write ( W )
Value
Range
(Analog
Only)
Unit
(Analog
Only)
Instance
Number
Comments
DmpSatMod
Bypass Damper Output Based
on Supply Air Temperature
BAV
R
0 - 100
%
16122
Only with Flexsys
Duct Hi Static
Status of the Duct Static High
Limit Switch:
1 = Normal - Active
0 = Fault - Inactive
BBI
R
-
-
12005
Duct Stat 1 Out
Duct Static 1 Input
BAI
R
0 - 2
inc wc
16102
Only with VAV or
Flexsys
Duct Stat 2 Out
Duct Static 2 Input
BAI
R
0 - 2
inc wc
16103
Only with VAV or
Flexsys
DuctHP
High Duct Pressure Alarm:
1 = Fault - Active
0 = No Fault - Inactive
BBV
R
-
-
15101
DuctSP
Derived Duct Static Input
BAV
R
0.0 – 5.0
in of wc
16120
Only with VAV or
Flexsys
DX Temp
Evaporator Coil Leaving
Temperature
BAI
R
0 - 120
Deg F
13019
Only with Flexsys
DxPrs
Minimum Allowable Pressure
Drop Across the Evaporator
Coil
BAV
R/W
0.2 - 1.0
in of wc
16005
Only with Flexsys
DxPrsMn
Minimum Pressure Drop
Across the Evaporator Coil to
Prove Air Flow
BAV
R/W
0.06 - 1.0
in of wc
16023
Only with Flexsys
E/W Econ En
BBV
15008
Not Applicable
E/W Min
BAV
16017
Not Applicable
E/W Mod
BAO
14004
Not Applicable
E/W Rat Mod
BAV
16114
Not Applicable
E/W Sat Mod
BAV
16113
Not Applicable
E/W Temp
BAI
13004
Not Applicable
E/WSadMod
Economizer PID Output Based
on Dew Point Temp
BAV
R
0 - 100
%
16124
Only with
Economizer,
FlexSys with Dew
Point Control
EcRat Enable
Economizer Return Air Temp
Control:
1 = Enabled
0 = Disabled
BBV
R/W
-
-
15007
EcSad Enable
Economizer Dew Point Temp
Control:
1 = Enabled
0 = Disabled
BBV
R/W
-
-
15009
Only with Flexsys
Continued on next page
TABLE 15 – BACnet MS/TP points (Cont.)
6
Summary of Contents for YSCD
Page 10: ...10 JOHNSON CONTROLS FORM 145 05 NOM2 807 THIS PAGE INTENTIONALLY LEFT BLANK ...
Page 12: ...12 JOHNSON CONTROLS FORM 145 05 NOM2 807 THIS PAGE INTENTIONALLY LEFT BLANK ...
Page 38: ...38 JOHNSON CONTROLS FORM 145 05 NOM2 807 THIS PAGE INTENTIONALLY LEFT BLANK ...
Page 46: ...46 JOHNSON CONTROLS FORM 145 05 NOM2 807 THIS PAGE INTENTIONALLY LEFT BLANK ...
Page 105: ...105 JOHNSON CONTROLS FORM 145 05 NOM2 807 LD13009 8 FIG 11 WIRING DIAGRAM POWER CIRCUIT ...