63
JOHNSON CONTROLS
FORM 145.05-NOM2 (807)
Point ID
Point Description
Variable
Type
Read ( R )
Write ( W )
Value
Range
(Analog
Only)
Unit
(Analog
Only)
Instance
Number
Comments
FCCVEn
Indicates if the Constant Volume
Fan Output is Forced On:
1 = On - Active
0 = Off - Inactive
BBV
R
-
-
15501
FCE/WMod
BBV
-
-
15518
Not Applicable
FCHtS1Cl
Indicates if the Stage 1 Heat or
Tristate Closed is Forced On:
1 = On - Active
0 = Off - Inactive
BBV
R
-
-
15511
FCHtS2Cl
Indicates if the Stage 2 Heat or
Tristate Closed is Forced On:
1 = On - Active
0 = Off - Inactive
BBV
R
-
-
15512
FCPmp Out
Indicates if the Pump Output is
Forced On:
1 = On - Active
0 = Off - Inactive
BBV
R
-
-
15503
FCVAVEn
Indicates if the VAV Supply
Fan Enable is Forced On:
1 = On - Active
0 = Off - Inactive
BBV
R
-
-
15502
FCVFDMod
Indicates if the VAV Modulating
Output is Forced On:
1 = On - Active
0 = Off - Inactive
BBV
R
-
-
15516
Freeze
Hydronic Coil Freezestat
Alarm:
1 = Fault - Active
0 = No Fault - Inactive
BBV
R
-
-
15102
Only with Hydronic
Heat
Freeze Stat
Freeze Stat Input:
1 = Closed - Active
0 = Open - Inactive
BBI
R
-
-
12006
Only with Hydronic
Heat
FRIDAYSCHED1
Turns the Friday Schedule 1
On and Off:
1 = On - Active
0 = Off - Inactive
BBV
R/W
-
-
878
FRIDAYSCHED10
Turns the Friday Schedule 10
On and Off:
1 = On - Active
0 = Off - Inactive
BBV
R/W
-
-
978
Continued on next page
TABLE 15 – BACnet MS/TP points (Cont.)
6
Summary of Contents for YSCD
Page 10: ...10 JOHNSON CONTROLS FORM 145 05 NOM2 807 THIS PAGE INTENTIONALLY LEFT BLANK ...
Page 12: ...12 JOHNSON CONTROLS FORM 145 05 NOM2 807 THIS PAGE INTENTIONALLY LEFT BLANK ...
Page 38: ...38 JOHNSON CONTROLS FORM 145 05 NOM2 807 THIS PAGE INTENTIONALLY LEFT BLANK ...
Page 46: ...46 JOHNSON CONTROLS FORM 145 05 NOM2 807 THIS PAGE INTENTIONALLY LEFT BLANK ...
Page 105: ...105 JOHNSON CONTROLS FORM 145 05 NOM2 807 LD13009 8 FIG 11 WIRING DIAGRAM POWER CIRCUIT ...