TABLE 13 – SETPOINT SCREEN PARAMETERS
DESCRIPTION
OPTIONS
DEFAULT VALUE
Unit Enable
On / Off
Off
Min DX Prs Drop (FlexSys units only)
0.2 “wc – 1.0”wc
0.5 “wc
POA DX Prs Drop (FlexSys units only)
.06”wc to 1.0”wc
0.1 “wc
AC – S/A Dew En (FlexSys units only)
ON / OFF
On
AC-S/A Dew Min (FlexSys units only)
40.0° F – 90.0° F
48.0° F
AC – S/A Dew Max (FlexSys units only)
40.0° F – 90.0° F
60.0° F
AC – S/A Dew Dif (FlexSys units only)
2.0° F – 10.0° F
5.0° F
AC-S/A Temp En
On / Off
On
Econ-S/A Tmp En
On / Off
On
AC/Econ-S/A SP
40° F – 90° F
55° F
AC-R/A Temp En
On / Off
Off
Econ-R/A Tmp En
On / Off
Off
AC/Econ – R/A SP
40° F – 90° F
75° F
Heat – S/A Tmp En
On / Off
On
Heat S/A Tmp SP
40° F – 115° F
110° F
Heat R/A Tmp En
On / Off
On
Heat R/A Tmp SP
40° F – 90° F
72° F
Fan-VAV/CV En
CV /VAV
VAV
Fan Sp BAS En (FlexSys units only)
On / Off
Off
VFD Sp % by BAS (FlexSys units only)
0% to 100%
0 %
Fan-S/A Pres SP
0.0” wc to 2.0” wc
1.0
Static Value
Low, High, Avg
Avg
H2O Econ En
On / Off
On
O/A Econ En
On / Off
Off
O/A Damper Min
0 % - 100 %
15%
Cond Valve Min
0% TO 100%
15%
Econ Valve Min
0% TO 100%
0%
The parameters in Table 13 can be programmed using the Setpoint screen.
6
Summary of Contents for YSCD
Page 10: ...10 JOHNSON CONTROLS FORM 145 05 NOM2 807 THIS PAGE INTENTIONALLY LEFT BLANK ...
Page 12: ...12 JOHNSON CONTROLS FORM 145 05 NOM2 807 THIS PAGE INTENTIONALLY LEFT BLANK ...
Page 38: ...38 JOHNSON CONTROLS FORM 145 05 NOM2 807 THIS PAGE INTENTIONALLY LEFT BLANK ...
Page 46: ...46 JOHNSON CONTROLS FORM 145 05 NOM2 807 THIS PAGE INTENTIONALLY LEFT BLANK ...
Page 105: ...105 JOHNSON CONTROLS FORM 145 05 NOM2 807 LD13009 8 FIG 11 WIRING DIAGRAM POWER CIRCUIT ...