59
JOHNSON CONTROLS
FORM 145.05-NOM2 (807)
Point ID
Point Description
Variable
Type
Read ( R )
Write ( W )
Value
Range
(Analog
Only)
Unit
(Analog
Only)
Instance
Number
Comments
Box Open Out
Output Signal to Open the VAV
Boxes:
1 = Active
0 = Inactive
BBO
R/W
-
-
11005
C/W Min
BAO
%
14001
Not Applicable
C/W Mod
BAV
-
-
16115
Not Applicable
Coil Stat Out
Coil Pressure Drop Across the
Evaporator Coil
BAV
R
0.0 - 5.0
in of wc
16103
Only with Flexsys
Comp
Quantity *
BAV
-
-
16211
Not Applicable
Comp Stages*
BAV
R/W
-
-
16213
CompA Disch Out
BAV
16104
Not Applicable
CompA En
BBO
-
-
11006
Not Applicable
CompA Suct Out
BAV
16105
Not Applicable
CompAH
BBV
-
-
15109
Not Applicable
CompAL
BBV
-
-
15105
Not Applicable
CompB Disch Out
BAV
16106
Not Applicable
CompB En
BBO
-
-
11007
Not Applicable
CompB Suct Out
BAV
16107
Not Applicable
CompBH
BBV
-
-
15108
Not Applicable
CompBL
BBV
-
-
15104
Not Applicable
CompC Disch Out
BAV
16108
Not Applicable
Continued on next page
TABLE 15 – BACnet MS/TP points (Cont.)
6
Summary of Contents for YSCD
Page 10: ...10 JOHNSON CONTROLS FORM 145 05 NOM2 807 THIS PAGE INTENTIONALLY LEFT BLANK ...
Page 12: ...12 JOHNSON CONTROLS FORM 145 05 NOM2 807 THIS PAGE INTENTIONALLY LEFT BLANK ...
Page 38: ...38 JOHNSON CONTROLS FORM 145 05 NOM2 807 THIS PAGE INTENTIONALLY LEFT BLANK ...
Page 46: ...46 JOHNSON CONTROLS FORM 145 05 NOM2 807 THIS PAGE INTENTIONALLY LEFT BLANK ...
Page 105: ...105 JOHNSON CONTROLS FORM 145 05 NOM2 807 LD13009 8 FIG 11 WIRING DIAGRAM POWER CIRCUIT ...