77
JOHNSON CONTROLS
FORM 145.05-NOM2 (807)
Point ID
Point Description
Variable
Type
Read ( R )
Write ( W )
Value
Range
(Analog
Only)
Unit
(Analog
Only)
Instance
Number
Comments
Ovr Sched
Identifi es if any Over Ride
Schedule is Active:
1 = On - Active
0 = Off - Inactive
BBO
R/W
-
-
871
Pump Out+
Indicates the Status of the
Pump Output
BBO
R/W
-
-
11003
R/A Temp
Return Air Temperature
BAI
R
0 -120
Deg F
13003
RatAcSp
Return Air Cooling
Temperature Set Point
BAV
R/W
55.0
– 80.0
Deg F
16002
RatHtSp
Return Air Heating
Temperature Set Point
BAV
R/W
50.0
– 80.0
Deg F
16004
S/A Hum Out
Supply Air Relative Humidity
BAV
R
0 -100
%
16602
Only with Flexsys
S/A Temp
Supply Air Temperature
BAI
R
0 -120
Deg F
13001
Sad
Supply Air Dew Point
Temperature
BAV
R
0 -120
Deg F
16125
Only with Flexsys
SadAcDif
Differential Temperature
Temperature Below Dew Point
BAV
R / W
2.0 -10.0
Deg F
16004
Only with Flexsys
with Dew Point
Control
SadAcMin
Minimum Supply Air
Temperature for Dew Point
Control
BAV
R / W
40.0
- 90.0
Deg F
16003
Only with Flexsys
with Dew Point
Control
SadAcMx
Maximum Supply Air
Temperature for Dew Point
Control
BAV
R / W
40.0
- 90.0
Deg F
16022
Only with Flexsys
with Dew Point
Control
Safe In
External Safety:
1 = Normal
0 = Fault
BBI
R
-
-
12003
Sap SP
Duct Static Pressure Set Point
BAV
R/W
0.0 – 2.0
In of wc
16013
Only with VAV or
Flexsys
SatAcSp
Supply Air Cooling
Temperature Set Point
BAV
R/W
48.0
– 70.0
Deg F
16001
SatHtSp
Supply Air Heating
Temperature Set Point
BAV
R/W
80.0
–125.0
Deg F
16003
SATURDAYSCHED1
Turns Saturday On / Off for
Schedule 1:
1= On - Active
0 = Off - Inactive
BBV
R/W
-
-
879
SATURDAYSCHED10
Turns Saturday On / Off for
Schedule 10:
1= On - Active
0 = Off - Inactive
BBV
R/W
-
-
979
SATURDAYSCHED11
Turns Saturday On / Off for
Schedule 11:
1= On - Active
0 = Off - Inactive
BBV
R/W
-
-
990
Continued on next page
TABLE 15 – BACnet MS/TP points (Cont.)
6
Summary of Contents for YSCD
Page 10: ...10 JOHNSON CONTROLS FORM 145 05 NOM2 807 THIS PAGE INTENTIONALLY LEFT BLANK ...
Page 12: ...12 JOHNSON CONTROLS FORM 145 05 NOM2 807 THIS PAGE INTENTIONALLY LEFT BLANK ...
Page 38: ...38 JOHNSON CONTROLS FORM 145 05 NOM2 807 THIS PAGE INTENTIONALLY LEFT BLANK ...
Page 46: ...46 JOHNSON CONTROLS FORM 145 05 NOM2 807 THIS PAGE INTENTIONALLY LEFT BLANK ...
Page 105: ...105 JOHNSON CONTROLS FORM 145 05 NOM2 807 LD13009 8 FIG 11 WIRING DIAGRAM POWER CIRCUIT ...