SECTION 9 – SERVICE AND TROUBLESHOOTING
Form 150.63-NM9
Issue date: 5/20/2021
9
PROBLEM
CAUSE
SOLUTION
MP / HPCO FAULT
1. Compressor internal motor
protector (MP) open.
1. Verify refrigerant charge is not low. Verify
superheat setting of 10°F to 15°F (5.6°C to
8.3°C). Verify compressor is not overloaded.
2. External overload tripped.
2. Determine cause and reset.
3. HPCO switch open.
3.
See High Press. Disch. Fault.
4. Defective HPCO switch.
4. Replace HPCO switch.
5. Defective CR relay.
5. Replace relay.
COMPRESSOR(S) WON’T
START
1. Demand not great enough.
1. No problem.
Consult Installation Manual to
aid in understanding compressor operation
and capacity control.
2. Defective water temperature
sensor.
2. Compare the display with a thermometer.
Should be within plus or minus 2 degrees.
See Service section for RWT/LWT temp./
voltage table.
3. Contactor/Overload failure.
3. Replace defective part.
4. Compressor failure.
4. Diagnose cause of failure and replace.
LACK OF COOLING EFFECT
1. Check DX Coil.
1. Contact the local Johnson Controls service
representative.
2. Improbeforeflow through the DX
Coil.
2. Reduce flow to within chiller design specs.
See Limitations in Installation section.
3. Low refrigerant charge. Low
suction pressure will be
observed.
3. Check subcooling and add charge as
needed.
Table 31 -
Troubleshooting (cont’d)
Summary of Contents for YCUL0020
Page 4: ...JOHNSON CONTROLS 4 Form 150 63 NM9 Issue date 5 20 2021 THIS PAGE IS INTENTIONALLY LEFT BLANK...
Page 10: ...JOHNSON CONTROLS 10 Form 150 63 NM9 Issue date 5 20 2021 THIS PAGE IS INTENTIONALLY LEFT BLANK...
Page 14: ...JOHNSON CONTROLS 14 Form 150 63 NM9 Issue date 5 20 2021 THIS PAGE IS INTENTIONALLY LEFT BLANK...
Page 40: ...JOHNSON CONTROLS 40 Form 150 63 NM9 Issue date 5 20 2021 THIS PAGE IS INTENTIONALLY LEFT BLANK...
Page 53: ...JOHNSON CONTROLS 53 Section 5 Technical data Form 150 63 NM9 Issue date 5 20 2021 5...
Page 55: ...JOHNSON CONTROLS 55 Section 5 Technical data Form 150 63 NM9 Issue date 5 20 2021 5...
Page 57: ...JOHNSON CONTROLS 57 Section 5 Technical data Form 150 63 NM9 Issue date 5 20 2021 5...
Page 59: ...JOHNSON CONTROLS 59 Section 5 Technical data Form 150 63 NM9 Issue date 5 20 2021 5...
Page 61: ...JOHNSON CONTROLS 61 Section 5 Technical data Form 150 63 NM9 Issue date 5 20 2021 5...
Page 63: ...JOHNSON CONTROLS 63 Section 5 Technical data Form 150 63 NM9 Issue date 5 20 2021 5...
Page 65: ...JOHNSON CONTROLS 65 Section 5 Technical data Form 150 63 NM9 Issue date 5 20 2021 5...
Page 67: ...JOHNSON CONTROLS 67 Section 5 Technical data Form 150 63 NM9 Issue date 5 20 2021 5...
Page 69: ...JOHNSON CONTROLS 69 Section 5 Technical data Form 150 63 NM9 Issue date 5 20 2021 5...
Page 71: ...JOHNSON CONTROLS 71 Section 5 Technical data Form 150 63 NM9 Issue date 5 20 2021 5...
Page 73: ...JOHNSON CONTROLS 73 Section 5 Technical data Form 150 63 NM9 Issue date 5 20 2021 5...
Page 75: ...JOHNSON CONTROLS 75 Section 5 Technical data Form 150 63 NM9 Issue date 5 20 2021 5...
Page 77: ...JOHNSON CONTROLS 77 Section 5 Technical data Form 150 63 NM9 Issue date 5 20 2021 5...
Page 79: ...JOHNSON CONTROLS 79 Section 5 Technical data Form 150 63 NM9 Issue date 5 20 2021 5...
Page 81: ...JOHNSON CONTROLS 81 Section 5 Technical data Form 150 63 NM9 Issue date 5 20 2021 5...
Page 83: ...JOHNSON CONTROLS 83 Section 5 Technical data Form 150 63 NM9 Issue date 5 20 2021 5...
Page 85: ...JOHNSON CONTROLS 85 Section 5 Technical data Form 150 63 NM9 Issue date 5 20 2021 5...
Page 87: ...JOHNSON CONTROLS 87 Section 5 Technical data Form 150 63 NM9 Issue date 5 20 2021 5...
Page 177: ...JOHNSON CONTROLS 177 Form 150 63 NM9 Issue date 5 20 2021 Notes...