136
Form 150.63-NM9
Issue date: 5/20/2021
SECTION 7 – UNIT CONTROLS
Option 14 – Refrigerant Type
R E F R I G E R A N T T Y P E
R - 4 0 7 C
Refrigerant type R-22, R-407C or R410A may be se-
lected under Service Mode. Refrigerant type is dis-
played under the OPTIONS key, but is only program-
mable in Service Mode.
Incorrect programming may cause dam-
age to compressors. R-410A MUST be
programmed.
Option 15 – Expansion Valve Type
E X P A N S I O N V A L V E T Y P E
T H E R M O S T A T I C
The expansion valve type must be thermostatic or elec-
tronic may be selected under Service Mode. Expansion
valve type is displayed under the OPTIONS key, but is
programmable in Service Mode.
Incorrect programming may cause dam-
age to compressors.
Also
see the Unit Keys Programming Quick Reference
List in Table 17.
Option 16 – Flash Card Update
F L A S H C A R D U P D A T E
D I S A B L E D
A Flash Card is used to input the operating program
into the unit IPU. A Flash Card is used instead of an
EPROM. Normally, a Flash Card update is not required
and the message above will be displayed.
If the operating software is to be updated, insert the
Flash Card into the Flash Card input port. Turn off the
unit switch and set the FLASH CARD UPDATE TO
“ENABLED” using the ↑ and ↓ keys.
F L A S H C A R D U P D A T E
E N A B L E D
Press the ENTER key and the following message will
be displayed until the update has been completed. The
keypad and display will not respond during the update.
DO NOT reset or power down the unit until the update
is completed.
F L A S H C A R D U P D A T I N G
P L E A S E W A I T . . .
After the update is completed, an automatic reboot will
occur. If an error occurred, the following message will
appear with the error code and no reboot will occur.
F L A S H C A R D U P D A T E
E R
R
O
R
XXXXX
If the update resulted in an error, the original program
will still be active. When an error occurs, ensure the
correct Flash Card was utilized. Incorrect unit software
will cause an error. If this is not the case, the Flash
Card is most likely defective or the IPU and I/O combo
board is bad.
Option 17 – Remote Temperature Reset
R E M O T E T E M P R E S E T
I
N
P U T
XXXXXXXXXXXXXX
Remote Temp Reset input selection is programmable
according to the type of input utilized. The following
options are available:
• DISABLED (default)
• 0.0 – 10.0 VDC
• 2.0 – 10.0 VDC
• 0.0 – 20.0 mA
• 4.0 – 20.0 mA
The options display message for Remote
Temp Reset Input only appears if the Temp
reset Option is enabled under Service
Mode.
Summary of Contents for YCUL0020
Page 4: ...JOHNSON CONTROLS 4 Form 150 63 NM9 Issue date 5 20 2021 THIS PAGE IS INTENTIONALLY LEFT BLANK...
Page 10: ...JOHNSON CONTROLS 10 Form 150 63 NM9 Issue date 5 20 2021 THIS PAGE IS INTENTIONALLY LEFT BLANK...
Page 14: ...JOHNSON CONTROLS 14 Form 150 63 NM9 Issue date 5 20 2021 THIS PAGE IS INTENTIONALLY LEFT BLANK...
Page 40: ...JOHNSON CONTROLS 40 Form 150 63 NM9 Issue date 5 20 2021 THIS PAGE IS INTENTIONALLY LEFT BLANK...
Page 53: ...JOHNSON CONTROLS 53 Section 5 Technical data Form 150 63 NM9 Issue date 5 20 2021 5...
Page 55: ...JOHNSON CONTROLS 55 Section 5 Technical data Form 150 63 NM9 Issue date 5 20 2021 5...
Page 57: ...JOHNSON CONTROLS 57 Section 5 Technical data Form 150 63 NM9 Issue date 5 20 2021 5...
Page 59: ...JOHNSON CONTROLS 59 Section 5 Technical data Form 150 63 NM9 Issue date 5 20 2021 5...
Page 61: ...JOHNSON CONTROLS 61 Section 5 Technical data Form 150 63 NM9 Issue date 5 20 2021 5...
Page 63: ...JOHNSON CONTROLS 63 Section 5 Technical data Form 150 63 NM9 Issue date 5 20 2021 5...
Page 65: ...JOHNSON CONTROLS 65 Section 5 Technical data Form 150 63 NM9 Issue date 5 20 2021 5...
Page 67: ...JOHNSON CONTROLS 67 Section 5 Technical data Form 150 63 NM9 Issue date 5 20 2021 5...
Page 69: ...JOHNSON CONTROLS 69 Section 5 Technical data Form 150 63 NM9 Issue date 5 20 2021 5...
Page 71: ...JOHNSON CONTROLS 71 Section 5 Technical data Form 150 63 NM9 Issue date 5 20 2021 5...
Page 73: ...JOHNSON CONTROLS 73 Section 5 Technical data Form 150 63 NM9 Issue date 5 20 2021 5...
Page 75: ...JOHNSON CONTROLS 75 Section 5 Technical data Form 150 63 NM9 Issue date 5 20 2021 5...
Page 77: ...JOHNSON CONTROLS 77 Section 5 Technical data Form 150 63 NM9 Issue date 5 20 2021 5...
Page 79: ...JOHNSON CONTROLS 79 Section 5 Technical data Form 150 63 NM9 Issue date 5 20 2021 5...
Page 81: ...JOHNSON CONTROLS 81 Section 5 Technical data Form 150 63 NM9 Issue date 5 20 2021 5...
Page 83: ...JOHNSON CONTROLS 83 Section 5 Technical data Form 150 63 NM9 Issue date 5 20 2021 5...
Page 85: ...JOHNSON CONTROLS 85 Section 5 Technical data Form 150 63 NM9 Issue date 5 20 2021 5...
Page 87: ...JOHNSON CONTROLS 87 Section 5 Technical data Form 150 63 NM9 Issue date 5 20 2021 5...
Page 177: ...JOHNSON CONTROLS 177 Form 150 63 NM9 Issue date 5 20 2021 Notes...