JOHNSON CONTROLS
134
Form 150.63-NM9
Issue date: 5/20/2021
SECTION 7 – UNIT CONTROLS
Option 4 – Local/Remote Control Type
L O C A L / R E M O T E M O D E L
L O
C A L
When programmed for LOCAL, an ISN or RCC con-
trol can be used to monitor only. The micro panel will
operate on locally programmed values and ignore all
commands from the remote devices. The condensing
unit will communicate and send data to the remote
monitoring devices.
or
L O C A L / R E M O T E M O D E
R E
M
O T E
This mode should be selected when an ISN or RCC
control is to be used to control the condensing unit.
This mode will allow the ISN to control the follow-
ing items: Remote Start/Stop, Cooling Setpoint, Load
Limit, and History Buffer Request. If the unit receives
no valid ISN transmission for 5 minutes, it will revert
back to the locally programmed values.
Option 5 – Unit Control Mode
C O N T R O L M O D E
S U C T I O N P R E S S U R E
Unit control is based on Suction Pressure Control.
or
C O N T R O L M O D E
D I S C H A R G E A I R
Unit control is based on Discharge Air Temp. Control.
Option 6 – Display Units
D I S P L A Y U N I T S
I M
P E R I A L
This mode displays system operating values in Impe-
rial units of °F or psig.
or
D I S P L A Y U N I T S
S I
This mode displays system operating values in Scien-
tific International units of °C or barg.
Option 7 – Lead/Lag Type
(two system units only)
L E A D / L A G C O N T R O L
M A N U A L S Y S 1 L E A D
SYS 1 selected as lead compressor. SYS 1 lead option
MUST be chosen if Hot Gas Bypass is installed.
or
L E A D / L A G C O N T R O L
M A N U A L S Y S 2 L E A D
SYS 2 selected as lead compressor.
or
L E A D / L A G C O N T R O L
A U T O
M
A T I C
Lead/lag between systems may be selected to help
equalize average run hours between systems on con-
densing units with 2 refrigerant systems. Auto lead/lag
allows automatic lead/lag of the two systems based on
an average run hours of the compressors in each sys-
tem. A new lead/lag assignment is made whenever all
compressors shut down. The microboard will then as-
sign the “lead” to the system with the shortest average
run time.
Option 8 – Condenser Fan Control Mode
F A N C O N T R O L
D I S C H A R G E P R E S S U R E
Condenser fans are controlled by discharge pressure
only. This mode may only be chosen when discharge
pressure transducers are installed.
F A N C O N T R O L
A M B I E N T
&
D S C H P R E S S
Condenser fans are controlled by ambient temperature
and discharge pressure. This mode must be chosen if
the discharge pressure transducers are not installed.
Summary of Contents for YCUL0020
Page 4: ...JOHNSON CONTROLS 4 Form 150 63 NM9 Issue date 5 20 2021 THIS PAGE IS INTENTIONALLY LEFT BLANK...
Page 10: ...JOHNSON CONTROLS 10 Form 150 63 NM9 Issue date 5 20 2021 THIS PAGE IS INTENTIONALLY LEFT BLANK...
Page 14: ...JOHNSON CONTROLS 14 Form 150 63 NM9 Issue date 5 20 2021 THIS PAGE IS INTENTIONALLY LEFT BLANK...
Page 40: ...JOHNSON CONTROLS 40 Form 150 63 NM9 Issue date 5 20 2021 THIS PAGE IS INTENTIONALLY LEFT BLANK...
Page 53: ...JOHNSON CONTROLS 53 Section 5 Technical data Form 150 63 NM9 Issue date 5 20 2021 5...
Page 55: ...JOHNSON CONTROLS 55 Section 5 Technical data Form 150 63 NM9 Issue date 5 20 2021 5...
Page 57: ...JOHNSON CONTROLS 57 Section 5 Technical data Form 150 63 NM9 Issue date 5 20 2021 5...
Page 59: ...JOHNSON CONTROLS 59 Section 5 Technical data Form 150 63 NM9 Issue date 5 20 2021 5...
Page 61: ...JOHNSON CONTROLS 61 Section 5 Technical data Form 150 63 NM9 Issue date 5 20 2021 5...
Page 63: ...JOHNSON CONTROLS 63 Section 5 Technical data Form 150 63 NM9 Issue date 5 20 2021 5...
Page 65: ...JOHNSON CONTROLS 65 Section 5 Technical data Form 150 63 NM9 Issue date 5 20 2021 5...
Page 67: ...JOHNSON CONTROLS 67 Section 5 Technical data Form 150 63 NM9 Issue date 5 20 2021 5...
Page 69: ...JOHNSON CONTROLS 69 Section 5 Technical data Form 150 63 NM9 Issue date 5 20 2021 5...
Page 71: ...JOHNSON CONTROLS 71 Section 5 Technical data Form 150 63 NM9 Issue date 5 20 2021 5...
Page 73: ...JOHNSON CONTROLS 73 Section 5 Technical data Form 150 63 NM9 Issue date 5 20 2021 5...
Page 75: ...JOHNSON CONTROLS 75 Section 5 Technical data Form 150 63 NM9 Issue date 5 20 2021 5...
Page 77: ...JOHNSON CONTROLS 77 Section 5 Technical data Form 150 63 NM9 Issue date 5 20 2021 5...
Page 79: ...JOHNSON CONTROLS 79 Section 5 Technical data Form 150 63 NM9 Issue date 5 20 2021 5...
Page 81: ...JOHNSON CONTROLS 81 Section 5 Technical data Form 150 63 NM9 Issue date 5 20 2021 5...
Page 83: ...JOHNSON CONTROLS 83 Section 5 Technical data Form 150 63 NM9 Issue date 5 20 2021 5...
Page 85: ...JOHNSON CONTROLS 85 Section 5 Technical data Form 150 63 NM9 Issue date 5 20 2021 5...
Page 87: ...JOHNSON CONTROLS 87 Section 5 Technical data Form 150 63 NM9 Issue date 5 20 2021 5...
Page 177: ...JOHNSON CONTROLS 177 Form 150 63 NM9 Issue date 5 20 2021 Notes...