![background image](http://html1.mh-extra.com/html/york/ycul0020/ycul0020_installation-operation-and-maintenance-manual_4219906127.webp)
JOHNSON CONTROLS
127
SECTION 7 – UNIT CONTROLS
Form 150.63-NM9
Issue date: 5/20/2021
7
R E M O T E S U C T I O N
P R E S S U R E C O N T R O L
This message indicates that the cooling setpoint is un-
der REMOTE control. When under remote control, the
cooling setpoint will be determined by a remote device
such as an ISN control. This message also indicates
that the control point is based on Suction Pressure.
Immediately after the control mode message is dis-
played, the COOLING SETPOINT entry screen will be
displayed. If the unit is programmed for Discharge Air
Temperature the following message will be displayed:
S E T P O I N T = 5 5 . 0 ° F
R A N G E = + / - 5 . 0 ° F
(Discharge Air Temperature control)
The above message shows the current Discharge Air
temperature SETPOINT at 55.0°F (notice the cursor
positioned under the number 5). Pressing either the
UP or DOWN arrow will change the setpoint in 0.5°F
increments. After using the UP and DOWN arrows to
adjust to the desired setpoint, the ENTER/ADV key
must be pressed to enter this number into memory and
advance to the RANGE SETPOINT.
This will be indicated by the cursor moving under the
RANGE setpoint. The ↑ (UP) and ↓ (DOWN) arrow
keys are used to set the RANGE, in 0.5 °F increments,
to the desired RANGE setpoint. After adjusting the set-
point, the ENTER/ADV key must be pressed to enter
the data into memory.
The Discharge Air temperature SETPOINT is pro-
grammed from 45°F (7.2°C) to 70°F (21.1°C). The
Control Range is programmed from 3.0°F (-16.1°C) to
10°F (-12.0°C).
If the unit was programmed for Suction Pressure con-
trol, the following message would be displayed instead
of the previous message.
S Y S X S P = 1 0 5 P S I G
R A N G E = + / - 3 P S I G
(Suction Pressure control)
The setpoint and range are programmed with the ↑ (UP)
and ↓ (DOWN) arrow, and ENTER/ADV key as de
-
scribed in the previous setpoint message. The setpoints
in Suction Pressure Control are the suction pressures
of each individual system on the condensing Unit and
will control to within plus or minus the cooling range.
On two system units, each system is controlled inde-
pendently of each other according to its own setpoint
and cooling range, so there will be two similar displays;
a setpoint and range for both system 1 and system 2.
The Suction Pressure SETPOINTS are programmable
from 60 psig to 90 psig. The Control Range is pro-
grammable from 2 psig to 10 psig.
Both Discharge Air Temperature and Suction Pressure
control are described in detail under the section on Ca-
pacity Control.
Pressing the COOLING SETPOINTS again, after set-
ting the “local” setpoint(s), will display the remote set-
point and cooling range. This display automatically up-
dates about every 2 seconds. Notice that these setpoints
are not “locally” programmable, but are controlled by a
remote device such as an ISN control. These setpoints
would only be valid if the unit was operating in the
REMOTE mode. The following messages illustrate
both Discharge Air Temperature and Suction Pressure
control respectively.
R E M S E T P = 5 5 . 0 ° F
R A N G E = + / - 5 . 0 ° F
(Discharge Air Temperature control)
R E M S P X = 1 0 5 P S I G
R A N G E = + / - 3 P S I G
(Suction Pressure control)
Pressing the COOLING SETPOINTS again will bring
up the display that allows the Maximum EMS-PWM
Temperature Reset to be programmed. This message is
shown below.
M A X E M S - P W M R E M O T E
T E M P R E S E T = + 2 0 ° F
The Temp Reset value is the maximum allowable reset
of the Discharge Air Temperature Setpoint. The set-
point can be reset upwards by the use of a contact clo-
sure on the PWM Temp Reset input (CTB1 terminals
13 - 20).
See the section on Operating Controls for a
detailed explanation of this feature.
As with the other setpoints, the ↑ (UP) Arrow and ↓
(DOWN) arrow keys are used to change the Temp Re-
set value. After using the UP and DOWN arrows to ad-
just to the desired setpoint, the ENTER/ADV key must
be pressed to enter this number into memory.
Summary of Contents for YCUL0020
Page 4: ...JOHNSON CONTROLS 4 Form 150 63 NM9 Issue date 5 20 2021 THIS PAGE IS INTENTIONALLY LEFT BLANK...
Page 10: ...JOHNSON CONTROLS 10 Form 150 63 NM9 Issue date 5 20 2021 THIS PAGE IS INTENTIONALLY LEFT BLANK...
Page 14: ...JOHNSON CONTROLS 14 Form 150 63 NM9 Issue date 5 20 2021 THIS PAGE IS INTENTIONALLY LEFT BLANK...
Page 40: ...JOHNSON CONTROLS 40 Form 150 63 NM9 Issue date 5 20 2021 THIS PAGE IS INTENTIONALLY LEFT BLANK...
Page 53: ...JOHNSON CONTROLS 53 Section 5 Technical data Form 150 63 NM9 Issue date 5 20 2021 5...
Page 55: ...JOHNSON CONTROLS 55 Section 5 Technical data Form 150 63 NM9 Issue date 5 20 2021 5...
Page 57: ...JOHNSON CONTROLS 57 Section 5 Technical data Form 150 63 NM9 Issue date 5 20 2021 5...
Page 59: ...JOHNSON CONTROLS 59 Section 5 Technical data Form 150 63 NM9 Issue date 5 20 2021 5...
Page 61: ...JOHNSON CONTROLS 61 Section 5 Technical data Form 150 63 NM9 Issue date 5 20 2021 5...
Page 63: ...JOHNSON CONTROLS 63 Section 5 Technical data Form 150 63 NM9 Issue date 5 20 2021 5...
Page 65: ...JOHNSON CONTROLS 65 Section 5 Technical data Form 150 63 NM9 Issue date 5 20 2021 5...
Page 67: ...JOHNSON CONTROLS 67 Section 5 Technical data Form 150 63 NM9 Issue date 5 20 2021 5...
Page 69: ...JOHNSON CONTROLS 69 Section 5 Technical data Form 150 63 NM9 Issue date 5 20 2021 5...
Page 71: ...JOHNSON CONTROLS 71 Section 5 Technical data Form 150 63 NM9 Issue date 5 20 2021 5...
Page 73: ...JOHNSON CONTROLS 73 Section 5 Technical data Form 150 63 NM9 Issue date 5 20 2021 5...
Page 75: ...JOHNSON CONTROLS 75 Section 5 Technical data Form 150 63 NM9 Issue date 5 20 2021 5...
Page 77: ...JOHNSON CONTROLS 77 Section 5 Technical data Form 150 63 NM9 Issue date 5 20 2021 5...
Page 79: ...JOHNSON CONTROLS 79 Section 5 Technical data Form 150 63 NM9 Issue date 5 20 2021 5...
Page 81: ...JOHNSON CONTROLS 81 Section 5 Technical data Form 150 63 NM9 Issue date 5 20 2021 5...
Page 83: ...JOHNSON CONTROLS 83 Section 5 Technical data Form 150 63 NM9 Issue date 5 20 2021 5...
Page 85: ...JOHNSON CONTROLS 85 Section 5 Technical data Form 150 63 NM9 Issue date 5 20 2021 5...
Page 87: ...JOHNSON CONTROLS 87 Section 5 Technical data Form 150 63 NM9 Issue date 5 20 2021 5...
Page 177: ...JOHNSON CONTROLS 177 Form 150 63 NM9 Issue date 5 20 2021 Notes...