SECTION 6 – COMMISSIONING
JOHNSON CONTROLS
2
FORM 150.63-CL2
ISSUE DATE: 03/12/2019
TABLE 1 -
SETPOINTS ENTRY LIST
OPTIONS
Display Language
Sys 1 Switch
Sys 2 Switch
Chilled Liquid
*
Ambient Control
Local/Remote Mode
Control Mode
Display Units
*
Lead/Lag Control
*
Fan Control
Manual Override
Current Feedback
** Soft Start
** Unit Type
** Refrigerant Type
** Expansion Valve Type
COOLING SETPOINTS
Cooling Setpoint
Range
EMS-PWM Max. Setpoint
PROGRAM
Discharge Pressure Cutout
Suct. Pressure Cutout
Low Amb. Temp. Cutout
Anti-Recycle Time
Fan Control On Pressure
Fan Differential Off Pressure
Total # of Compressors
*
Number of Fans/System
*
Unit/Sys Voltage
Unit ID
*
Sys 1 Superheat Setpoint
*
Sys 2 Superheat Setpoint
* Not on All Models
** Viewable Only
Place the Unit Switch in the control panel to the
“ON” position. As each compressor cycles ON, en-
sure that the discharge pressure rises and the suc-
tion pressure decreases. If this does not occur, the
compressor being tested is operating in the reverse
direction and must be corrected. After verifying prop-
er compressor rotation, turn the Unit Switch to “OFF.”
The discharge air or suction pressure
setpoint may need to be temporarily
lowered to ensure all compressors cycle
“ON.”
This unit uses scroll compressors which
can only operate in one direction. Failure
to observe this will lead to compressor
failure.
6. Turn system 1 “off” and system 2 “on” (refer to Op-
tion 2 under “UNIT keys” in Section 7 for more in-
formation on system switches). ...............................
Place the Unit Switch in the control panel to the
“ON” position. As each compressor cycles “on”, en-
sure that the discharge pressure rises and the suc-
tion pressure decreases. If this does not occur, the
compressor being tested is operating in the reverse
direction and must be corrected. After verifying prop-
er compressor rotation, turn the Unit Switch to “OFF”.
The chilled liquid setpoint may need to
be temporarily lowered to ensure all com-
pressors cycle “ON”.
Summary of Contents for YCUL0020
Page 4: ...JOHNSON CONTROLS 4 Form 150 63 NM9 Issue date 5 20 2021 THIS PAGE IS INTENTIONALLY LEFT BLANK...
Page 10: ...JOHNSON CONTROLS 10 Form 150 63 NM9 Issue date 5 20 2021 THIS PAGE IS INTENTIONALLY LEFT BLANK...
Page 14: ...JOHNSON CONTROLS 14 Form 150 63 NM9 Issue date 5 20 2021 THIS PAGE IS INTENTIONALLY LEFT BLANK...
Page 40: ...JOHNSON CONTROLS 40 Form 150 63 NM9 Issue date 5 20 2021 THIS PAGE IS INTENTIONALLY LEFT BLANK...
Page 53: ...JOHNSON CONTROLS 53 Section 5 Technical data Form 150 63 NM9 Issue date 5 20 2021 5...
Page 55: ...JOHNSON CONTROLS 55 Section 5 Technical data Form 150 63 NM9 Issue date 5 20 2021 5...
Page 57: ...JOHNSON CONTROLS 57 Section 5 Technical data Form 150 63 NM9 Issue date 5 20 2021 5...
Page 59: ...JOHNSON CONTROLS 59 Section 5 Technical data Form 150 63 NM9 Issue date 5 20 2021 5...
Page 61: ...JOHNSON CONTROLS 61 Section 5 Technical data Form 150 63 NM9 Issue date 5 20 2021 5...
Page 63: ...JOHNSON CONTROLS 63 Section 5 Technical data Form 150 63 NM9 Issue date 5 20 2021 5...
Page 65: ...JOHNSON CONTROLS 65 Section 5 Technical data Form 150 63 NM9 Issue date 5 20 2021 5...
Page 67: ...JOHNSON CONTROLS 67 Section 5 Technical data Form 150 63 NM9 Issue date 5 20 2021 5...
Page 69: ...JOHNSON CONTROLS 69 Section 5 Technical data Form 150 63 NM9 Issue date 5 20 2021 5...
Page 71: ...JOHNSON CONTROLS 71 Section 5 Technical data Form 150 63 NM9 Issue date 5 20 2021 5...
Page 73: ...JOHNSON CONTROLS 73 Section 5 Technical data Form 150 63 NM9 Issue date 5 20 2021 5...
Page 75: ...JOHNSON CONTROLS 75 Section 5 Technical data Form 150 63 NM9 Issue date 5 20 2021 5...
Page 77: ...JOHNSON CONTROLS 77 Section 5 Technical data Form 150 63 NM9 Issue date 5 20 2021 5...
Page 79: ...JOHNSON CONTROLS 79 Section 5 Technical data Form 150 63 NM9 Issue date 5 20 2021 5...
Page 81: ...JOHNSON CONTROLS 81 Section 5 Technical data Form 150 63 NM9 Issue date 5 20 2021 5...
Page 83: ...JOHNSON CONTROLS 83 Section 5 Technical data Form 150 63 NM9 Issue date 5 20 2021 5...
Page 85: ...JOHNSON CONTROLS 85 Section 5 Technical data Form 150 63 NM9 Issue date 5 20 2021 5...
Page 87: ...JOHNSON CONTROLS 87 Section 5 Technical data Form 150 63 NM9 Issue date 5 20 2021 5...
Page 177: ...JOHNSON CONTROLS 177 Form 150 63 NM9 Issue date 5 20 2021 Notes...