SECTION 8 – UNIT OPERATION
Form 150.63-NM9
Issue date: 5/20/2021
8
Suction pressure control
The setpoint in Suction Pressure Control is the suction
pressures each individual system on the condensing
unit will control to within plus or minus the cooling
range. The Setpoint High Limit is the Setpoint plus the
Cooling Range. The Setpoint Low Limit is the Setpoint
minus the Cooling Range. Each system is controlled
independently of each other according to its setpoint
and cooling range.
Each system must have its own zone thermostat. If the
respective zone thermostat is closed, the lead compres-
sor on that system will be energized. In addition the
liquid line solenoid to that system will be energized.
Upon energizing any compressor the 60 second Anti-
Coincidence timer will be initiated.
If after 150 seconds of run-time the suction pressure is
still above the Setpoint High Limit, the next compres-
sor in sequence will be energized. Additional loading
stages are energized at a rate of once every 150 seconds
if the suction pressure remains above the Setpoint High
Limit. Each system will have its own load timer of 150
seconds.
If the suction pressure falls below the Setpoint High
Limit and greater than the Setpoint Low Limit, load-
ing and unloading do not occur. This area of control is
called the control range.
If the suction pressure falls below the Setpoint Low
Limit, unloading (compressors cycling OFF) occurs at
a rate of 30 seconds beforesystem. The zone thermostat
must be satisfied before the last compressor in the sys-
tem cycles OFF, even if the suction pressure is below
the Setpoint Low Limit.
Hot Gas Bypass solenoid will be energized as the last
stage of unloading. If the zone thermostat calls for
cooling when the suction pressure is below the Set-
point Low Limit, the first stage compressor will be en-
ergized with the hot gas solenoid.
It should be noted that the zone thermostat has ultimate
control. As long as the zone thermostat is calling for
cooling, at least one compressor will be running, re-
gardless of whether the suction pressure is below Set-
point Low Limit.
illustrates loading and unloading in Suction
Pressure Control Mode. See the section on
Figure 41 -
Suction Pressure Control
30 second
control range
150 second
unloading
(no compressor staging)
loading
117 psig (8.0 barg)
126 psig (8.7 barg)
Setpoint
121 psig (8.3 barg)
Setpoint = 121 psig (8.3 barg)
Control Range = 5 psig ( 0.35 barg)
Setpoint
Low Limit
Setpoint
High Limit
Summary of Contents for YCUL0020
Page 4: ...JOHNSON CONTROLS 4 Form 150 63 NM9 Issue date 5 20 2021 THIS PAGE IS INTENTIONALLY LEFT BLANK...
Page 10: ...JOHNSON CONTROLS 10 Form 150 63 NM9 Issue date 5 20 2021 THIS PAGE IS INTENTIONALLY LEFT BLANK...
Page 14: ...JOHNSON CONTROLS 14 Form 150 63 NM9 Issue date 5 20 2021 THIS PAGE IS INTENTIONALLY LEFT BLANK...
Page 40: ...JOHNSON CONTROLS 40 Form 150 63 NM9 Issue date 5 20 2021 THIS PAGE IS INTENTIONALLY LEFT BLANK...
Page 53: ...JOHNSON CONTROLS 53 Section 5 Technical data Form 150 63 NM9 Issue date 5 20 2021 5...
Page 55: ...JOHNSON CONTROLS 55 Section 5 Technical data Form 150 63 NM9 Issue date 5 20 2021 5...
Page 57: ...JOHNSON CONTROLS 57 Section 5 Technical data Form 150 63 NM9 Issue date 5 20 2021 5...
Page 59: ...JOHNSON CONTROLS 59 Section 5 Technical data Form 150 63 NM9 Issue date 5 20 2021 5...
Page 61: ...JOHNSON CONTROLS 61 Section 5 Technical data Form 150 63 NM9 Issue date 5 20 2021 5...
Page 63: ...JOHNSON CONTROLS 63 Section 5 Technical data Form 150 63 NM9 Issue date 5 20 2021 5...
Page 65: ...JOHNSON CONTROLS 65 Section 5 Technical data Form 150 63 NM9 Issue date 5 20 2021 5...
Page 67: ...JOHNSON CONTROLS 67 Section 5 Technical data Form 150 63 NM9 Issue date 5 20 2021 5...
Page 69: ...JOHNSON CONTROLS 69 Section 5 Technical data Form 150 63 NM9 Issue date 5 20 2021 5...
Page 71: ...JOHNSON CONTROLS 71 Section 5 Technical data Form 150 63 NM9 Issue date 5 20 2021 5...
Page 73: ...JOHNSON CONTROLS 73 Section 5 Technical data Form 150 63 NM9 Issue date 5 20 2021 5...
Page 75: ...JOHNSON CONTROLS 75 Section 5 Technical data Form 150 63 NM9 Issue date 5 20 2021 5...
Page 77: ...JOHNSON CONTROLS 77 Section 5 Technical data Form 150 63 NM9 Issue date 5 20 2021 5...
Page 79: ...JOHNSON CONTROLS 79 Section 5 Technical data Form 150 63 NM9 Issue date 5 20 2021 5...
Page 81: ...JOHNSON CONTROLS 81 Section 5 Technical data Form 150 63 NM9 Issue date 5 20 2021 5...
Page 83: ...JOHNSON CONTROLS 83 Section 5 Technical data Form 150 63 NM9 Issue date 5 20 2021 5...
Page 85: ...JOHNSON CONTROLS 85 Section 5 Technical data Form 150 63 NM9 Issue date 5 20 2021 5...
Page 87: ...JOHNSON CONTROLS 87 Section 5 Technical data Form 150 63 NM9 Issue date 5 20 2021 5...
Page 177: ...JOHNSON CONTROLS 177 Form 150 63 NM9 Issue date 5 20 2021 Notes...