Physical data
Table 45: YV28 to YV30 physical data
Models
Component
YV28
YV30
Nominal tonnage
27.5
30
ARI cooling performance
2 Stage
4 Stage
2 Stage
4 Stage
Gross capacity @ ARI A point (Btu)
320,163
318,311
344,378
339,064
ARI net capacity (Btu)
308,000
306,000
336,000
330,000
EER
10.8
1
/ 10.5
2
10.8
/ 10.5
10.9
/ 10.8
10.9
/ 10.8
IEER CV
12.5
/ 11.8
n/a
13.3
/ 13.0
n/a
IEER with Intellispeed
14.4
/ 13.8
n/a
14.4
/ 14.0
n/a
IEER with VAV
n/a
15.2
/ 14.6
n/a
15.1
/ 14.6
CFM
10517
10590
9362
9683
System power (KW)
25.2
24.6
28.4
27.4
Refrigerant type
R-410A
R-410A
R-410A
R-410A
Refrigerant charge (lb-oz)
System 1
14-12
14-04
14-12
14-12
System 2
13-08
13-14
14.00
13-15
ARI heating performance
Heating model
N(S)1
N(S)3
N(S)1
N(S)3
Heating type
Stg. Low
Stg. High
Stg. Low
Stg. High
1st stage heat input (K Btu)
320
400
320
400
2nd stage heat input (K Btu)
400
220
400
220
1st stage heat output (K Btu)
259
324
259
324
2nd stage heat output (K Btu)
324
178
324
178
Steady state efficiency (%)
81
81
81
81
No. of burners
9
9/5
9
9/5
No. of stages / Turn down
2/1.25
2/1.82
2/1.25
2/1.82
Temperature rise range (ºF)
25-35
35-60
20-35
35-55
Gas limit setting (ºF) (top/bottom)
150
150/150
150
150/170
Gas piping connection (in.)
3/4
1 1/4
3/4
1 1/4
Dimensions (in.)
Length
180
Width
90
Height
70
Operating weight (lb)
4078
4105
Compressors
2 Stage
4 Stage
2 Stage
4 Stage
Type
Scroll
Scroll
Scroll
Scroll
Quantity
2
3
2
3
Unit capacity steps (%)
50 / 100
24 / 51 / 76 /100
50 / 100
24 / 52 / 76 /100
Condenser coil data
Face area (Sq. Ft.)
51.2
61.6
Type
MCHX
MCHX
Thickness (mm)
20
20
FPI
23
23
Circuitry type
2-Pass
2-Pass
Evaporator coil data
Face area (sq. ft.)
34.4
34.4
Rows
3
3
Fins per inch
15
15
Tube diameter
3/8
3/8
Circuitry type
Intertwined
Intertwined
Refrigerant control
TXV
TXV
Condenser fan data
Quantity
4
4
Fan diameter (in.)
30
30
Type
Prop
Prop
Drive type
Direct
Direct
Number of motors
4
4
Motor HP each
1
1
RPM
1140
1140
Nominal total CFM
28530
29800
Belt drive evap fan data
Installation Manual: YORK
®
Sun™ Select YV28 to YV50
62
Johnson Controls Ducted Systems
Summary of Contents for Sun Select YV28
Page 2: ...Tested in accordance with ...
Page 105: ...Installation Manual YORK Sun Select YV28 to YV50 105 Johnson Controls Ducted Systems ...
Page 106: ...Installation Manual YORK Sun Select YV28 to YV50 106 Johnson Controls Ducted Systems ...
Page 107: ...Installation Manual YORK Sun Select YV28 to YV50 107 Johnson Controls Ducted Systems ...
Page 108: ...Installation Manual YORK Sun Select YV28 to YV50 108 Johnson Controls Ducted Systems ...
Page 109: ...Installation Manual YORK Sun Select YV28 to YV50 109 Johnson Controls Ducted Systems ...