Table 58: Belt tension
Belt tension
Size
Motor-Static
Deflection
force (lb)
Deflection
distance (in.)
Max PRM
7.5HP - STD
5.78
0.4
10HP - MED
4.48
0.4
YV28
15HP - HIGH
5.72
0.4
1100
7.5HP - STD
5.9
0.4
10HP - MED
6.91
0.4
YV30
15HP - HIGH
5.93
0.4
1100
7.5HP - STD
5.78
0.4
10HP - MED
4.48
0.4
YV35
15HP - HIGH
5.72
0.4
1150
10HP - STD
7.42
0.4
15HP - MED
8.85
0.4
YV40
20HP - HIGH
7.23
0.4
1150
10HP - STD
7.42
0.4
15HP - MED
8.85
0.4
YV50
20HP - HIGH
7.23
0.4
1150
Drive selection
1. Determine the required airflow.
2. Calculate or measure the amount of external
static pressure.
3. With the operating point determined from
the previous steps, locate this point on the
appropriate supply air blower performance
table. Linear interpolation may be necessary.
4. Note the RPM and BHP from the previous
step and locate the appropriate motor and/or
drive.
5. Review the BHP compared to the motor
options available. Select the appropriate
motor and/or drive.
6. Review the RPM range for the motor options
available. Select the appropriate drive if
multiple drives are available for the chosen
motor.
7. Determine the turns open to obtain the
required operation point.
Example
1. 9000 CFM
2. 1.2 IWG
3. Using the supply air blower performance table
below, the following data point was located:
810 RPM and 4.82 BHP.
4. Using the following RPM selection table, Size X
and Model Y is found.
5. 4.82 BHP does not exceed the maximum
continuous BHP rating of any of the three
motor options, so all three motors are still
eligible for selection.
6. 810 RPM falls within the range of the 7.5-HP
drive.
7. Using the 7.5-HP motor, 2.5 turns open
achieves 810 RPM.
Table 59: Example supply air blower performance
Available external static pressure - IWG
0.3
0.4
0.6
0.8
1
1.2
1.4
1.6
1.8
2
2.2
2.4
2.5
Air flow
(CFM)
RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
Standard 7.5HP and field drive
Standard 7.5HP and drive
Medium 10HP and drive
High 20 HP and drive
8000
573 2.29 599 2.53 649 2.98 696 3.39 742 3.78 786 4.16 828 4.55 869 4.95 910 5.36 949 5.79 988 6.25 1026 6.75 1045 7.00
9000
606 2.92 631 3.15 678 3.59 724 4.01 768 4.41 810 4.82 851 5.24 892 5.67 931 6.13 970 6.60 1007 7.12 1045 7.66 1063 7.95
10000
642 3.62 665 3.85 711 4.29 754 4.72 796 5.15 837 5.58 877 6.04 916 6.51 955 7.00 992 7.53 1029 8.09 1066 8.69 1084 9.01
11000
680 4.41 702 4.64 745 5.09 787 5.54 827 6.00 867 6.47 906 6.96 943 7.47 981 8.01 1017 8.59 1054 9.21 1089 9.87 1107 10.21
12000
721 5.31 741 5.55 782 6.02 822 6.50 861 6.99 899 7.49 936 8.02 973 8.58 1009 9.18 1045 9.81 1080 10.49 1115 11.21 1132 11.58
13000
763 6.36 783 6.60 822 7.10 860 7.61 897 8.14 933 8.69 969 9.26 1005 9.88 1040 10.52 1075 11.22 1109 11.95 1143 12.74
-
-
Note:
Blower performance includes gas heat exchangers and 2-in. filters. See the Static resistance
table for additional applications. See the RPM selection table to determine the required motor sheave
setting and to determine the maximum continuous BHP. kW = BHP x 0.93
Table 60: Example RPM selection
Model
HP
Max BHP
Motor
sheave
Blower
sheave
6 turns open 5 turns open 4 turns open 3 turns open 2 turns open 1 turn open Fully closed
7.5
8.24
1VP65 - 1 3/8
1B5V124
717
745
772
800
827
855
882
10
10.90
2VP60- 1 3/8
2B5V94
848
884
920
956
992
1028
1064
YV28
15
16.13
2VP60- 1 5/8
2B5V86
945
985
1026
1066
1106
1147
n/a
Installation Manual: YORK
®
Sun™ Select YV28 to YV50
79
Johnson Controls Ducted Systems
Summary of Contents for Sun Select YV28
Page 2: ...Tested in accordance with ...
Page 105: ...Installation Manual YORK Sun Select YV28 to YV50 105 Johnson Controls Ducted Systems ...
Page 106: ...Installation Manual YORK Sun Select YV28 to YV50 106 Johnson Controls Ducted Systems ...
Page 107: ...Installation Manual YORK Sun Select YV28 to YV50 107 Johnson Controls Ducted Systems ...
Page 108: ...Installation Manual YORK Sun Select YV28 to YV50 108 Johnson Controls Ducted Systems ...
Page 109: ...Installation Manual YORK Sun Select YV28 to YV50 109 Johnson Controls Ducted Systems ...