Table 44: YV28 to YV50 VFD Customer supplied high static with modulating power exhaust
Comp. 1
Comp. 2
Comp. 3
Min
disconnect
rating
Min
disconnect
rating/120V
trans
Size
(tons)
Nominal
unit
voltage
RLA LRA RLA LRA RLA LRA
OD fan
motors
each
FLA
OD fan
motors
each
FLA
Supply
blower
motor
FLA
Supply
blower
motor
LRA
Power
exhaus
t VFD
FLA
Power
exhaus
t motor
LRA
120 V
trans
FLA
MCA
A
Max
f/b
size
A
FLA
LRA
MCA
with
120 V
trans
A
Max
f/b
size
with
120V
trans
A
FLA
LRA
208-3-60 41.0 304 22.4 149 22.4 149
4.0
21.0
36.0
234
9.6
21.0
14.4
158
175
170
962
172
200
186
976
230-3-60 41.0 304 22.4 149 22.4 149
4.2
21.0
36.0
234
9.6
21.0
13.0
158
175
170
962
171
200
185
975
460-3-60 19.2 147 10.6 75 10.6 75
2.1
10.5
18.0
117
4.8
10.5
6.5
76
90
82
477
83
100
90
484
YV28
(27.5)
575-3-60 16.7 122 7.7
54
7.7
54
1.6
7.8
14.2
95.94
4.9
7.8
5.2
62
75
66
373
67
80
72
378
208-3-60 44.2 315
25
164
25
164
4.0
21.0
36.0
234
9.6
21.0
14.4
167
200
179 1003 181
225
196 1017
230-3-60 44.2 315
25
164
25
164
4.2
21.0
36.0
234
9.6
21.0
13.0
168
200
180 1003 181
200
195 1016
460-3-60 22.4 158 12.8 100 12.8 100
2.1
10.5
18.0
117
4.8
10.5
6.5
85
100
91
538
91
110
99
545
YV30
(30)
575-3-60 18.6 136 9.6
78
9.6
78
1.6
7.8
14.2
95.94
4.9
7.8
5.2
68
80
73
435
73
90
79
440
208-3-60 48.1 351 27.6 191 27.6 191
4
21.0
36.0
234
9.6
21.0
14.4
177
225
190 1093 191
225
206 1107
230-3-60 48.1 351 27.6 191 27.6 191
4.2
21.0
36.0
234
9.6
21.0
13.0
178
225
191 1093 191
225
206 1106
460-3-60 24.7 197 12.8 100 12.8 100
2.1
10.5
18.0
117
4.8
10.5
6.5
88
110
94
577
94
110
101
584
YV35
(35)
575-3-60 22.4 135 9.6
78
9.6
78
1.6
7.8
14.2
95.94
4.9
7.8
5.2
73
90
77
434
78
100
83
439
208-3-60 48.1 351 27.6 191 27.6 191
4
21.0
48.0
312
15.2
39.6
14.4
195
225
210 1208 209
250
226 1223
230-3-60 48.1 351 27.6 191 27.6 191
4.2
21.0
48.0
312
15.2
39.6
13.0
195
225
211 1208 208
250
226 1221
460-3-60 24.7 197 12.8 100 12.8 100
2.1
10.5
24.0
156
8.2
19.8
6.5
97
110
105
635
104
125
112
641
YV40
(40)
575-3-60 22.4 135 9.6
78
9.6
78
1.6
7.8
19.1
126
6.1
15.8
5.2
79
100
84
480
84
100
90
485
208-3-60 67.3 485 39.1 267 39.1 267
7.2
39.6
48.0
312
15.2
39.6
14.4
254
300
273 1569 269
325
290 1583
230-3-60 67.3 485 39.1 267 39.1 267
6.8
39.6
48.0
312
15.2
39.6
13.0
253
300
271 1569 266
325
286 1582
460-3-60 32.7 215 18.6 142 18.6 142
3.4
19.8
24.0
156
8.2
19.8
6.5
124
150
133
774
130
150
141
780
YV50
(50)
575-3-60 26.3 175 15.4 103 15.4 103
2.7
15.8
19.1
126
6.1
15.8
5.2
100
125
107
602
105
125
113
607
Installation Manual: YORK
®
Sun™ Select YV28 to YV50
61
Johnson Controls Ducted Systems
Summary of Contents for Sun Select YV28
Page 2: ...Tested in accordance with ...
Page 105: ...Installation Manual YORK Sun Select YV28 to YV50 105 Johnson Controls Ducted Systems ...
Page 106: ...Installation Manual YORK Sun Select YV28 to YV50 106 Johnson Controls Ducted Systems ...
Page 107: ...Installation Manual YORK Sun Select YV28 to YV50 107 Johnson Controls Ducted Systems ...
Page 108: ...Installation Manual YORK Sun Select YV28 to YV50 108 Johnson Controls Ducted Systems ...
Page 109: ...Installation Manual YORK Sun Select YV28 to YV50 109 Johnson Controls Ducted Systems ...