VFD Customer supplied high static
Note:
•
MCA = minimum circuit ampacity
•
f/b = fuse/breaker
•
Fuse is a dual element, time delay type
•
Breaker is a HACR type per NEC
Table 42: YV28 to YV50 VFD Customer supplied high static without power exhaust
Comp. 1
Comp. 2
Comp. 3
Min
disconnect
rating
Min
disconnect
rating/120
V trans
Size
(tons)
Nominal
unit
voltage
RLA LRA RLA LRA RLA LRA
OD fan
motors
each
FLA
OD fan
motors
each
RLA
Supply
blower
motor
FLA
Supply
blower
motor
LRA
120 V
trans
FLA
MCA
A
Max
f/b
size
A
FLA
LRA
MCA
with
120 V
trans
A
Max
f/b
size
with
120 V
trans
A
FLA
LRA
208-3-60 41.0 304 22.4 149 22.4 149
4.0
21.0
36.0
234
14.4
148 175.0 158
920.0
162 200.0 175.0 934.4
230-3-60 41.0 304 22.4 149 22.4 149
4.2
21.0
36.0
234
13.0
149 175.0 159
920.0
162 200.0 174.3 933.0
460-3-60 19.2 147 10.6 75 10.6 75
2.1
10.5
18.0
117
6.5
72
90.0
77
456.0
78
90.0 84.3 462.5
YV28
(27.5)
575-3-60 16.7 122 7.7
54
7.7
54
1.6
7.8
14.2
95.94
5.2
57
70.0
61
357.1
62
75.0 66.6 362.3
208-3-60 44.2 315
25
164
25
164
4.0
21.0
36.0
234
14.4
157 200.0 168
961.0
172 200.0 184.7 975.4
230-3-60 44.2 315
25
164
25
164
4.2
21.0
36.0
234
13.0
158 200.0 169
961.0
171 200.0 184.0 974.0
460-3-60 22.4 158 12.8 100 12.8 100
2.1
10.5
18.0
117
6.5
80
100.0
86
517.0
87
100.0 93.0 523.5
YV30
(30)
575-3-60 18.6 136 9.6
78
9.6
78
1.6
7.8
14.2
95.94
5.2
63
80.0
67
419.1
68
80.0 73.1 424.3
208-3-60 48.1 351 27.6 191 27.6 191
4
21.0
36.0
234
14.4
167 200.0 179 1051.0 182 225.0 195.2 1065.4
230-3-60 48.1 351 27.6 191 27.6 191
4.2
21.0
36.0
234
13.0
168 200.0 180 1051.0 181 225.0 194.5 1064.0
460-3-60 24.7 197 12.8 100 12.8 100
2.1
10.5
18.0
117
6.5
83
100.0
88
556.0
89
110.0 95.7 562.5
YV35
(35)
575-3-60 22.4 135 9.6
78
9.6
78
1.6
7.8
14.2
95.94
5.2
68
90.0
72
418.1
73
90.0 77.5 423.3
208-3-60 48.1 351 27.6 191 27.6 191
4
21.0
48.0
312
14.4
179 225.0 192 1129.0 194 225.0 209.0 1143.4
230-3-60 48.1 351 27.6 191 27.6 191
4.2
21.0
48.0
312
13.0
180 225.0 193 1129.0 193 225.0 208.3 1142.0
460-3-60 24.7 197 12.8 100 12.8 100
2.1
10.5
24.0
156
6.5
89
110.0
95
595.0
95
110.0 102.6 601.5
YV40
(40)
575-3-60 22.4 135 9.6
78
9.6
78
1.6
7.8
19.1
126
5.2
73
90.0
77
448.2
78
100.0 83.1 453.4
208-3-60 67.3 485 39.1 267 39.1 267
7.2
39.6
48.0
312
14.4
239 300.0 256 1489.4 254 300.0 272.2 1503.8
230-3-60 67.3 485 39.1 267 39.1 267
6.8
39.6
48.0
312
13.0
238 300.0 254 1489.4 251 300.0 268.8 1502.4
460-3-60 32.7 215 18.6 142 18.6 142
3.4
19.8
24.0
156
6.5
116 125.0 124
734.2
122 150.0 131.1 740.7
YV50
(50)
575-3-60 26.3 175 15.4 103 15.4 103
2.7
15.8
19.1
126
5.2
94
110.0 100
570.2
99
125.0 106.0 575.4
Table 43: YV28 to YV50 VFD Customer supplied high static on/off power exhaust
Comp. 1
Comp. 2
Comp. 3
Electric heat option
field installed kit
Min
disconnect
rating
Min
disconnect
rating/120V
trans
Size
(tons)
Nominal
unit
voltage
RLA LRA RLA LRA RLA LRA
OD fan
motors
each
FLA
Supply
blower
motor
FLA
120V
trans
FLA
Mod
el
kW Stages
A
MCA
A
Max
f/b
size
A
FLA
LRA
MCA
with
120V
trans
A
Max
f/b
size
with
120V
trans
A
FLA
LRA
208-3-60 41.0 304 22.4 149 22.4 149
4.0
21.0
36.0 234 4.0
21.0
14.4
156
175
168
962
170
200
184
976
230-3-60 41.0 304 22.4 149 22.4 149
4.2
21.0
36.0 234 4.2
21.0
13.0
157
175
169
962
170
200
184
975
460-3-60 19.2 147 10.6 75 10.6 75
2.1
10.5
18.0 117 2.1
10.5
6.5
76
90
82
477
82
100
89
484
YV28
(27.5)
575-3-60 16.7 122 7.7
54
7.7
54
1.6
7.8
14.2 95.94 1.6
7.8
5.2
60
75
64
373
65
80
70
378
208-3-60 44.2 315
25
164
25
164
4.0
21.0
36.0 234 4.0
21.0
14.4
165
200
177 1003 180
200
194 1017
230-3-60 44.2 315
25
164
25
164
4.2
21.0
36.0 234 4.2
21.0
13.0
166
200
179 1003 179
200
194 1016
460-3-60 22.4 158 12.8 100 12.8 100
2.1
10.5
18.0 117 2.1
10.5
6.5
84
100
90
538
91
110
98
545
YV30
(30)
575-3-60 18.6 136 9.6
78
9.6
78
1.6
7.8
14.2 95.94 1.6
7.8
5.2
66
80
71
435
71
90
77
440
208-3-60 48.1 351 27.6 191 27.6 191
4
21.0
36.0 234
4
21.0
14.4
175
200
188 1093 190
225
204 1107
230-3-60 48.1 351 27.6 191 27.6 191
4.2
21.0
36.0 234 4.2
21.0
13.0
177
200
189 1093 190
225
204 1106
460-3-60 24.7 197 12.8 100 12.8 100
2.1
10.5
18.0 117 2.1
10.5
6.5
87
110
93
577
94
110
101
584
YV35
(35)
575-3-60 22.4 135 9.6
78
9.6
78
1.6
7.8
14.2 95.94 1.6
7.8
5.2
71
90
75
434
76
90
81
439
208-3-60 48.1 351 27.6 191 27.6 191
4
21.0
48.0 312 7.2
39.6
14.4
194
225
209 1208 208
250
226 1223
230-3-60 48.1 351 27.6 191 27.6 191
4.2
21.0
48.0 312 6.8
39.6
13.0
194
225
209 1208 207
250
224 1221
460-3-60 24.7 197 12.8 100 12.8 100
2.1
10.5
24.0 156 3.4
19.8
6.5
96
110
103
635
102
125
110
641
YV40
(40)
575-3-60 22.4 135 9.6
78
9.6
78
1.6
7.8
19.1 126 2.7
15.8
5.2
78
100
83
480
83
100
89
485
208-3-60 67.3 485 39.1 267 39.1 267
7.2
39.6
48.0 312 7.2
39.6
14.4
254
300
272 1569 268
325
289 1583
230-3-60 67.3 485 39.1 267 39.1 267
6.8
39.6
48.0 312 6.8
39.6
13.0
251
300
269 1569 264
325
284 1582
460-3-60 32.7 215 18.6 142 18.6 142
3.4
19.8
24.0 156 3.4
19.8
6.5
122
150
131
774
129
150
139
780
YV50
(50)
575-3-60 26.3 175 15.4 103 15.4 103
2.7
15.8
19.1 126 2.7
15.8
5.2
99
125
106
602
104
125
112
607
Installation Manual: YORK
®
Sun™ Select YV28 to YV50
60
Johnson Controls Ducted Systems
Summary of Contents for Sun Select YV28
Page 2: ...Tested in accordance with ...
Page 105: ...Installation Manual YORK Sun Select YV28 to YV50 105 Johnson Controls Ducted Systems ...
Page 106: ...Installation Manual YORK Sun Select YV28 to YV50 106 Johnson Controls Ducted Systems ...
Page 107: ...Installation Manual YORK Sun Select YV28 to YV50 107 Johnson Controls Ducted Systems ...
Page 108: ...Installation Manual YORK Sun Select YV28 to YV50 108 Johnson Controls Ducted Systems ...
Page 109: ...Installation Manual YORK Sun Select YV28 to YV50 109 Johnson Controls Ducted Systems ...