Table 51: Smart Equipment™ economizer board - analog inputs
Location
Board label
Cover
label
Description
Function and comments
R
24V~
24 VAC hot supplied for the outdoor air humidity sensor
Connects through circuit trace to 24V~ IN pin HOT
IN3
OAH
0-10 VDC positive input from the Outdoor Air Humidity
sensor
OAH parameter reports input status (0-100%H). Used in outdoor air enthalpy
calculation for dual enthalpy economizer free cooling changeover.
C
COM
24 VAC common/0-10 VDC negative for the outdoor air
humidity sensor
Connects through circuit trace to 24V~ IN pin COM
R
24V~
24 VAC hot supplied for the supply air humidity sensor
Connects through circuit trace to 24V~ IN pin HOT
IN4
SAH
0-10 VDC positive input from the Supply Air Humidity
sensor
SAH parameter reports input status (0-100%H). Unused in current control
revision.
C
COM
24 VAC common/0-10 VDC negative for the supply air
humidity sensor
Connects through circuit trace to 24V~ IN pin COM
R
24V~
24 VAC hot supplied for the indoor air quality sensor
Connects through circuit trace to 24V~ IN pin HOT
IN5
IAQ
0-10 VDC positive input from the Indoor Air Quality sensor
IAQRange parameter sets the CO2 parts per million measured by the indoor
air quality sensor when it outputs 10 VDC; IAQ parameter reports input status
(0-5000ppm). Used for demand ventilation functions if the NetIAQ parameter
indicates ‑Unrel.
C
COM
24 VAC common/0-10 VDC negative for the indoor air
quality sensor
Connects through circuit trace to 24V~ IN pin COM
R
24V~
24 VAC hot supplied for the outdoor air quality sensor
Connects through circuit trace to 24V~ IN pin HOT
IN6
OAQ
0-10 VDC positive input from the Outdoor Air Quality
sensor
OAQRange parameter sets the CO2 parts per million measured by the outdoor
air quality sensor when it outputs 10 VDC; OAQ parameter reports input status
(0-5000ppm). Used for demand ventilation function when DVent-Mode selection
is Diff between IAQ and OAQ and the NetOAQ parameter indicates ‑Unrel.
C
COM
24 VAC common/0-10 VDC negative for the outdoor air
quality sensor
Connects through circuit trace to 24V~ IN pin COM
R
24V~
24 VAC hot supplied for the air monitoring station sensor Connects through circuit trace to 24V~ IN pin HOT
IN7
FR AIR
0-10 VDC positive input from the air monitoring station
sensor
MOA-Range parameter sets the cubic feet per minute/liters per second
measured by the air monitoring station sensor when it outputs 10 VDC; Fr Air
parameter reports input status (0-50000CFM/23595lps). Used for economizer
minimum position reset in speed-controlled indoor blower applications.
C
COM
24 VAC common/0-10 VDC negative for the air monitoring
station sensor
Connects through circuit trace to 24V~ IN pin COM
R
24V~
24 VAC hot supplied for the building pressure sensor
Connects through circuit trace to 24V~ IN pin HOT
IN8
BLDG PRES 0-5 VDC positive input from the Building Pressure sensor
BldgPres parameter reports input status (-.250-.250”/w/-.062-.062kPa). Used
for modulating power exhaust functions when ExFType selection is Modulating
Damper or Variable Frequency Fan.
H
C
COM
24 VAC common/0-5 VDC negative for the building
pressure sensor
Connects through circuit trace to 24V~ IN pin COM
Table 52: Smart Equipment™ economizer board - LED details
Location
Board label Cover label
Description
Function and comments
POWER
POWER
Green UCB power indicator
Lit indicates 24 VAC is present at 24V~ IN COM and HOT pins
FAULT
FAULT
Red networking error and firmware error indicator
1/10th second on/off flashing indicates a networking error (polarity, addressing,
etc.) or a firmware error (likely correctable with re-loading from USB flash drive)
B
SA BUS
SA BUS
Green UCB SA bus communication transmission indicator
Lit/flickering indicates UCB-to-economizer board SA bus communication
is currently active, off indicates the economizer board is awaiting SA bus
communication
Installation Manual: YORK
®
Sun™ Select YV28 to YV50
75
Johnson Controls Ducted Systems
Summary of Contents for Sun Select YV28
Page 2: ...Tested in accordance with ...
Page 105: ...Installation Manual YORK Sun Select YV28 to YV50 105 Johnson Controls Ducted Systems ...
Page 106: ...Installation Manual YORK Sun Select YV28 to YV50 106 Johnson Controls Ducted Systems ...
Page 107: ...Installation Manual YORK Sun Select YV28 to YV50 107 Johnson Controls Ducted Systems ...
Page 108: ...Installation Manual YORK Sun Select YV28 to YV50 108 Johnson Controls Ducted Systems ...
Page 109: ...Installation Manual YORK Sun Select YV28 to YV50 109 Johnson Controls Ducted Systems ...