Charging tables
Table 70: 27.5 ton charging table - System 1
Air flow
indoor DB/WB
Outdoor
DB °F
Suction
pressure
psig
Suction
temp °F
Liquid
pressure
psig
Liquid
temp °F
Delta T,
indoor
DB °F
75
111
46
259
78
28
85
113
47
304
88
27
300 cfm/ton;
80/62
95
115
48
352
97
26
75
122
51
258
81
23
85
124
52
304
90
23
300 cfm/ton;
80/67
95
127
53
352
99
22
75
134
56
257
84
19
85
137
57
303
93
18
300 cfm/ton;
80/72
95
139
58
352
101
17
75
111
46
260
78
23
85
113
46
305
88
23
300 cfm/ton;
75/62
95
115
48
353
97
22
75
118
49
259
79
24
85
120
50
304
89
23
400 cfm/ton;
80/62
95
122
50
352
98
23
75
130
54
258
82
19
85
132
55
304
91
19
400 cfm/ton;
80/67
95
134
56
352
100
18
75
142
59
258
85
15
85
145
60
303
94
15
400 cfm/ton;
80/72
95
147
61
353
103
14
75
118
49
260
79
20
85
120
50
305
88
19
400 cfm/ton;
75/62
95
122
50
354
98
19
Table 71: 27.5 ton charging table - System 2
Air flow
indoor DB/WB
Outdoor
DB °F
Suction
pressure
psig
Suction
temp °F
Liquid
pressure
psig
Liquid
temp °F
Delta T
indoor
DB °F
75
113
46
253
77
28
85
115
47
297
86
27
300 cfm/ton;
80/62
95
117
48
345
96
26
75
124
51
252
79
23
85
126
52
296
88
23
300 cfm/ton;
80/67
95
129
53
345
97
22
75
137
56
250
81
19
85
139
57
295
90
18
300 cfm/ton;
80/72
95
141
58
344
99
17
75
113
46
254
77
23
85
115
47
298
86
23
300 cfm/ton;
75/62
95
117
48
346
96
22
75
120
49
253
78
24
85
122
50
297
87
23
400 cfm/ton;
80/62
95
123
51
345
97
23
75
132
54
251
80
19
85
134
55
296
89
19
400 cfm/ton;
80/67
95
136
56
345
98
18
75
144
59
249
83
15
85
146
60
295
91
15
400 cfm/ton;
80/72
95
149
61
344
100
14
75
120
49
253
77
20
85
122
50
298
87
19
400 cfm/ton;
75/62
95
124
51
346
97
19
Table 72: 30 ton charging table - System 1
Air flow
indoor DB/WB
Outdoor
DB °F
Suction
pressure
psig
Suction
temp °F
Liquid
pressure
psig
Liquid
temp °F
Delta T
indoor
DB °F
75
110
51
250
81
28
85
112
52
293
90
28
300 cfm/ton;
80/62
95
114
53
340
100
27
75
121
56
249
83
24
85
123
56
293
92
23
300 cfm/ton;
80/67
95
126
57
340
102
22
75
133
61
251
84
19
85
135
61
294
94
18
300 cfm/ton;
80/72
95
137
62
341
104
18
75
109
50
251
80
24
85
111
51
294
89
23
300 cfm/ton;
75/62
95
114
52
341
99
23
75
117
54
250
82
24
85
119
55
293
91
24
400 cfm/ton;
80/62
95
120
55
340
101
23
75
129
58
250
83
20
85
130
59
293
93
19
400 cfm/ton;
80/67
95
132
60
341
102
19
75
140
63
252
84
16
85
142
64
294
95
15
400 cfm/ton;
80/72
95
145
65
341
105
14
75
116
54
250
81
20
85
118
54
294
90
20
400 cfm/ton;
75/62
95
120
55
342
100
19
Table 73: 30 ton charging table - System 2
Air flow
indoor DB/WB
Outdoor
DB °F
Suction
pressure
psig
Suction
temp °F
Liquid
pressure
psig
Liquid
temp °F
Delta T
indoor
DB °F
75
112
50
248
80
28
85
114
51
291
90
28
300 cfm/ton;
80/62
95
117
52
337
100
27
75
123
55
247
83
24
85
126
56
290
92
23
300 cfm/ton;
80/67
95
128
57
337
102
22
75
134
59
248
83
19
85
137
61
291
94
18
300 cfm/ton;
80/72
95
140
62
338
103
18
75
112
50
249
80
24
85
114
51
292
89
23
300 cfm/ton;
75/62
95
116
52
339
99
23
75
119
53
247
82
24
85
121
54
290
91
24
400 cfm/ton;
80/62
95
123
55
337
101
23
75
132
58
247
83
20
85
133
59
290
93
19
400 cfm/ton;
80/67
95
135
60
337
103
19
75
142
63
249
83
16
85
143
63
296
91
15
400 cfm/ton;
80/72
95
147
65
338
104
14
75
118
53
248
81
20
85
120
54
292
90
20
400 cfm/ton;
75/62
95
123
55
339
100
19
Installation Manual: YORK
®
Sun™ Select YV28 to YV50
93
Johnson Controls Ducted Systems
Summary of Contents for Sun Select YV28
Page 2: ...Tested in accordance with ...
Page 105: ...Installation Manual YORK Sun Select YV28 to YV50 105 Johnson Controls Ducted Systems ...
Page 106: ...Installation Manual YORK Sun Select YV28 to YV50 106 Johnson Controls Ducted Systems ...
Page 107: ...Installation Manual YORK Sun Select YV28 to YV50 107 Johnson Controls Ducted Systems ...
Page 108: ...Installation Manual YORK Sun Select YV28 to YV50 108 Johnson Controls Ducted Systems ...
Page 109: ...Installation Manual YORK Sun Select YV28 to YV50 109 Johnson Controls Ducted Systems ...