Table 14: YV28 to YV50 Constant volume medium static modulating power exhaust
Comp. 1
Comp. 2
Min
disconnect
rating
Min
disconnect
rating/120V
trans
Size
(tons)
Nominal
unit
voltage
RLA LRA RLA LRA
OD fan
motors
each
FLA
OD fan
motors
each
FLA
Supply
blower
motor
FLA
Supply
blower
motor
LRA
Power
exh
VFD FLA
Power
exh
motor
LRA
120 V
trans
FLA
MCA
A
Max
f/b
size
A
FLA
LRA
MCA
with
120 V
trans
A
Max
f/b
size
with
120V
trans
A
FLA
LRA
208-3-60 41.0 304 41.0 304
4.0
21.0
25.0
173.44
9.6
21.0
14.4
143
175
152
907
157
175
169
922
230-3-60 41.0 304 41.0 304
4.2
21.0
25.0
173.44
9.6
21.0
13.0
144
175
153
907
157
175
168
920
460-3-60 19.2 147 19.2 147
2.1
10.5
12.5
86.72
4.8
10.5
6.5
69
80
74
444
75
90
81
450
YV28
(27.5)
575-3-60 16.7 122 16.7 122
1.6
7.8
10.0
71.77
4.9
7.8
5.2
59
75
63
363
64
80
69
368
208-3-60 44.2 315 44.2 315
4.0
21.0
25.0
173.44
9.6
21.0
14.4
150
175
160
929
164
200
176
944
230-3-60 44.2 315 44.2 315
4.2
21.0
25.0
173.44
9.6
21.0
13.0
151
175
161
929
164
200
176
942
460-3-60 22.4 158 22.4 158
2.1
10.5
12.5
86.72
4.8
10.5
6.5
76
90
81
466
83
100
89
472
YV30
(30)
575-3-60 18.6 136 18.6 136
1.6
7.8
10.0
71.77
4.9
7.8
5.2
63
80
67
391
68
80
73
396
208-3-60 48.1 351 48.1 351
4.0
21.0
25.0
173.44
9.6
21.0
14.4
159
200
169 1001 173
200
185 1016
230-3-60 48.1 351 48.1 351
4.2
21.0
25.0
173.44
9.6
21.0
13.0
160
200
170 1001 173
200
185 1014
460-3-60 24.7 197 24.7 197
2.1
10.5
12.5
86.72
4.8
10.5
6.5
81
100
86
544
88
110
94
550
YV35
(35)
575-3-60 22.4 135 22.4 135
1.6
7.8
10.0
71.77
4.9
7.8
5.2
72
90
76
389
77
90
82
394
208-3-60 48.1 351 48.1 351
4.0
21.0
36.0
234
15.2
39.6
14.4
175
200
188 1099 190
225
204 1114
230-3-60 48.1 351 48.1 351
4.2
21.0
36.0
234
15.2
39.6
13.0
176
200
189 1099 189
225
204 1112
460-3-60 24.7 197 24.7 197
2.1
10.5
18.0
117
8.2
19.8
6.5
90
110
97
593
97
110
104
599
YV40
(40)
575-3-60 22.4 135 22.4 135
1.6
7.8
14.2
95.94
6.1
15.8
5.2
77
90
82
429
82
100
88
434
208-3-60 67.3 485 67.3 485
7.2
39.6
36.0
234
15.2
39.6
14.4
231.4 275
247 1442 246
300
263 1456
230-3-60 67.3 485 67.3 485
6.8
39.6
36.0
234
15.2
39.6
13.0
229.8 275
245 1442 243
300
260 1455
460-3-60 32.7 215 32.7 215
3.4
19.8
18.0
117
8.2
19.8
6.5
113
125
121
666
120
150
128
672
YV50
(50)
575-3-60 26.3 175 26.3 175
2.7
15.8
14.2
95.94
6.1
15.8
5.2
90.3
110
96
541
95
110
102
546
Installation Manual: YORK
®
Sun™ Select YV28 to YV50
41
Johnson Controls Ducted Systems
Summary of Contents for Sun Select YV28
Page 2: ...Tested in accordance with ...
Page 105: ...Installation Manual YORK Sun Select YV28 to YV50 105 Johnson Controls Ducted Systems ...
Page 106: ...Installation Manual YORK Sun Select YV28 to YV50 106 Johnson Controls Ducted Systems ...
Page 107: ...Installation Manual YORK Sun Select YV28 to YV50 107 Johnson Controls Ducted Systems ...
Page 108: ...Installation Manual YORK Sun Select YV28 to YV50 108 Johnson Controls Ducted Systems ...
Page 109: ...Installation Manual YORK Sun Select YV28 to YV50 109 Johnson Controls Ducted Systems ...