Table 32: YV28 to YV50 VFD four-stage medium static with modulating exhaust
Comp. 1
Comp. 2
Comp. 3
Min
disconnect
rating
Min
disconnect
rating/120V
trans
Size
(tons)
Nominal
unit
voltage
RLA LRA RLA LRA RLA LRA
OD fan
motors
each
FLA
OD fan
motors
each
FLA
Supply
blower
motor
FLA
Supply
blower
motor
LRA
Power
exhaus
t VFD
FLA
Power
exhaus
t motor
LRA
120 V
trans
FLA
MCA
A
Max
f/b
size
A
FLA
LRA
MCA
with
120 V
trans
A
Max
f/b
size
with
120V
trans
A
FLA
LRA
208-3-60 41.0 304 22.4 149 22.4 149
4.0
21.0
28.0
173.44
9.6
21.0
14.4
150
175
160
901
164
200
177
916
230-3-60 41.0 304 22.4 149 22.4 149
4.2
21.0
28.0
173.44
9.6
21.0
13.0
150
175
161
901
163
200
176
914
460-3-60 19.2 147 10.6 75 10.6 75
2.1
10.5
14.0
86.72
4.8
10.5
6.5
72
90
78
447
79
90
85
453
YV28
(27.5)
575-3-60 16.7 122 7.7
54
7.7
54
1.6
7.8
11.0
71.77
4.9
7.8
5.2
59
75
63
349
64
80
69
354
208-3-60 44.2 315
25
164
25
164
4.0
21.0
28.0
173.44
9.6
21.0
14.4
159
200
170
942
173
200
187
957
230-3-60 44.2 315
25
164
25
164
4.2
21.0
28.0
173.44
9.6
21.0
13.0
160
200
171
942
173
200
186
955
460-3-60 22.4 158 12.8 100 12.8 100
2.1
10.5
14.0
86.72
4.8
10.5
6.5
81
100
86
508
87
100
94
514
YV30
(30)
575-3-60 18.6 136 9.6
78
9.6
78
1.6
7.8
11.0
71.77
4.9
7.8
5.2
65
80
69
411
70
80
75
416
208-3-60 48.1 351 27.6 191 27.6 191
4.0
21.0
28.0
173.44
9.6
21.0
14.4
169
200
180 1032 183
225
197 1047
230-3-60 48.1 351 27.6 191 27.6 191
4.2
21.0
28.0
173.44
9.6
21.0
13.0
170
200
181 1032 183
225
196 1045
460-3-60 24.7 197 12.8 100 12.8 100
2.1
10.5
14.0
86.72
4.8
10.5
6.5
84
100
89
547
90
110
97
553
YV35
(35)
575-3-60 22.4 135 9.6
78
9.6
78
1.6
7.8
11.0
71.77
4.9
7.8
5.2
70
90
73
410
75
90
79
415
208-3-60 48.1 351 27.6 191 27.6 191
4.0
21.0
42.0
234
15.2
39.6
14.4
189
225
203 1130 203
250
220 1145
230-3-60 48.1 351 27.6 191 27.6 191
4.2
21.0
42.0
234
15.2
39.6
13.0
189
225
204 1130 202
250
219 1143
460-3-60 24.7 197 12.8 100 12.8 100
2.1
10.5
21.0
117
8.2
19.8
6.5
94
110
101
596
101
125
109
602
YV40
(40)
575-3-60 22.4 135 9.6
78
9.6
78
1.6
7.8
18.0
95.94
6.1
15.8
5.2
78
100
83
450
83
100
89
455
208-3-60 67.3 485 39.1 267 39.1 267
7.2
39.6
42.0
234
15.2
39.6
14.4
248
300
266 1491 263
325
283 1505
230-3-60 67.3 485 39.1 267 39.1 267
6.8
39.6
42.0
234
15.2
39.6
13.0
247
300
264 1491 260
325
279 1504
460-3-60 32.7 215 18.6 142 18.6 142
3.4
19.8
21.0
117
8.2
19.8
6.5
121
150
130
735
127
150
137
741
YV50
(50)
575-3-60 26.3 175 15.4 103 15.4 103
2.7
15.8
18.0
95.94
6.1
15.8
5.2
99
110
106
572
104
125
112
577
Installation Manual: YORK
®
Sun™ Select YV28 to YV50
53
Johnson Controls Ducted Systems
Summary of Contents for Sun Select YV28
Page 2: ...Tested in accordance with ...
Page 105: ...Installation Manual YORK Sun Select YV28 to YV50 105 Johnson Controls Ducted Systems ...
Page 106: ...Installation Manual YORK Sun Select YV28 to YV50 106 Johnson Controls Ducted Systems ...
Page 107: ...Installation Manual YORK Sun Select YV28 to YV50 107 Johnson Controls Ducted Systems ...
Page 108: ...Installation Manual YORK Sun Select YV28 to YV50 108 Johnson Controls Ducted Systems ...
Page 109: ...Installation Manual YORK Sun Select YV28 to YV50 109 Johnson Controls Ducted Systems ...