AYK550 User’s Manual
Start-Up
GROUP 98 OPTIONS
9802 Comm Prot Sel
Not Sel
GROUP 99 START-UP DATA
9901 Language
English (AM)
9902 Applic Macro
HVAC Default
9904 Motor Ctrl Mode
Scalar:Freq
9905 Motor Nom Volt
V
9906 Motor Nom Curr
A
9907 Motor Nom Freq
60 Hz
9908 Motor Nom Speed
9909 Motor Nom power
hp
9910 ID Run
Off
GROUP 01 OPERATING DATA
0102 Speed
0103 Output Freq
0104 Current
0105 Torque
0106 Power
0107 DC Bus Voltage
0109 Output Voltage
0110 Drive Temp
0111 External Ref 1
0112 External Ref 2
0113 Ctrl Location
0114 Run Time (R)
0115 kWh Counter (R)
0116 Appl Blk Output
0118 DI 1-3 Status
0119 DI 4-6 Status
0120 AI 1
0121 AI 2
0122 RO 1-3 Status
0123 RO 4-6 Status
0124 AO 1
0125 AO 2
0126 PID 1 Output
0127 PID 2 Output
0128 PID 1 Setpnt
0129 PID 2 Setpnt
0130 PID 1 Fbk
0131 PID 2 Fbk
0132 PID 1 Deviation
0133 PID 2 Deviation
0134 Comm RO Word
0135 Comm Value 1
0136 Comm Value 2
0137 Process Variable 1
0138 Process Variable 2
0139 Process Variable 3
0140 Run Time
0141 MWh Counter
0142 Revolution Cntr
0143 Drive On Time Hi
0144 Drive On Time Lo
0145 Motor Temp
GROUP 03 FB ACTUAL SIGNALS
0301 FB Command Word 1
0000 hex
0302 FB Command Word 2
0000 hex
0303 FB Sts Word 1
0000 hex
0304 FB Sts Word 2
0000 hex
0305 Fault Word 1
0000 hex
0306 Fault Word 2
0000 hex
0307 Fault Word 3
0000 hex
0308 Alarm Word 1
0000 hex
0309 Alarm Word 2
0000 hex
GROUP 04 FAULT HISTORY
0401 Last Fault
No Record
0402 Fault Time 1
0 d
0403 Fault Time 2
00:00:00
0404 Speed At Fit
0 rpm
0405 Freq At Fit
0.0 Hz
0406 Voltage At Fit
0.0 V
0407 Current At Fit
0.0 A
0408 Torque At Fit
0.0%
0409 Status At Fit
0000 hex
0410 DI 1-3 At Fit
0 0 0
0411 DI 4-6 At Fit
0 0 0
0412 Previous Fault 1
No Record
0413 Previous Fault 2
No Record
GROUP 10 START/STOP/DIR
1001 Ext1 Commands
DI1
1002 Ext2 Commands
DI1
1003 Direction
Forward
GROUP 11 REFERENCE SELECT
1101 Keypad Ref Sel
Ref1 (Hz/rpm)
1102 Ext1/Ext2 Sel
Ext1
1103 Ref1 Select
AI1
1104 Ref1 Min
1542
1105 Ref1 Max
60.0 Hz
1106 Ref2 Select
PID1out
1107 Ref2 Min
0.0%
1108 Ref2 Max
100.0%
GROUP 12 CONSTANT SPEEDS
1201 Const Speed Sel
D3
1202 Const Speed 1
6.0 Hz
1203 Const Speed 2
12.0 Hz
1204 Const Speed 3
18.0 Hz
1205 Const Speed 4
24.0 Hz
1206 Const Speed 5
30.0 Hz
1207 Const Speed 6
48.0 Hz
1208 Const Speed 7
60.0 Hz
1209 Timed Mode Sel
CS1/CS2
GROUP 13 ANALOG INPUTS
1301 Minimum AI1
20%
1302 Maximum AI1
100.0%
1303 Filter AI1
0.1 s
1304 Minimum AI2
20.0%
1305 Maximum AI2
100.0%
1306 Filter AI2
0.1 s
GROUP 14 RELAY OUTPUTS
1401 Relay Output 1
Ready
1402 Relay Output 2
Run
1403 Relay Output 3
Fault (-1)
1404 Relay 1 On Delay
0.0 s
1405 Relay 1 Off Delay
0.0 s
1406 Relay 2 On Delay
0.0 s
1407 Relay 2 Off Delay
0.0 s
1408 Relay 3 On Delay
0.0 s
1409 Relay 3 Off Delay
0.0 s
1410 Relay Output 4
Not Sel
1411 Relay Output 5
Not Sel
1412 Relay Output 6
Not Sel
1413 Relay 4 On Delay
0.0 s
1414 Relay 4 Off Delay
0.0 s
1415 Relay 5 On Delay
0.0 s
1416 Relay 5 Off Delay
0.0 s
1417 Relay 6 On Delay
0.0 s
1418 Relay 6 Off Delay
0.0 s
GROUP 15 ANALOG OUTPUT
1501 AO1 Content Sel
Output Freq
1502 AO1 Content Min
0.0 Hz
1503 AO1 Content Max
60.0 Hz
1504 Minimum AO1
4.0 mA
1505 Maximum AO1
20.0 mA
1506 Filter AO1
0.1 s
1507 AO2 Content Sel
Current
1508 AO2 Content Min
0.0 Hz
1509 AO2 Content Max
60.0 Hz
1510 Minimum AO2
4.0 mA
1511 Maximum AO2
20.0 mA
1512 Filter AO2
0.1 s
GROUP 16 SYSTEM CONTROLS
1601 Run Enable
Not Sel
1602 Parameter Lock
Open
1603 Pass Code
0
1604 Fault Reset Sel
Keypad
1605 User Par Set Chg
Not Sel
1606 Local Lock
Not Sel
1607 Parameter Save
Done
1608 Start Enable 1
DI4
1609 Start Enable 2
Not Sel
GROUP 17 OVERRIDE
1701 Override Sel
(DI6)
1702 Override Freq
0.0 Hz
1705 Override
Off
GROUP 20 LIMITS
2003 Max Current
1.1*In
2006 Undervolt ctrl
Enable (Time)
2007 Minimum Freq
15 Hz
2008 Maximum Freq
60.0 Hz
GROUP 21 START/STOP
2101 Start Function
Flying
2102 Stop Function
Coast
2103 DC Magn Time
0.30 s
2104 DC Hold
Not Sel
2106 DC Cirr Ref
0%
2107 DC Brake Time
0.0 s
2108 Start Inhibit
Off
2109 Em Stop Sel
Not Sel
2110 Torq Boost Curr
100%
GROUP 22 ACCEL/DECEL
2201 Acc/Dec 1/2 Sel
Not Sel
2202 Acceler Time 1
30.0 s
2203 Deceler Time 1
30.0 s
2204 Ramp Shape 1
Linear
2205 Acceler Time 2
60.0 s
2206 Deceler Time 2
60.0 s
2207 Ramp Shape 2
Linear
2208 Em Dec Time
1.0 s
2209 Ramp Input 0
Not Sel
GROUP 23 SPEED CONTROL
2301 Prop Gain
3.00
2302 Integration Time
2.50 s
2303 Derivation Time
ms
2304 Acc Compensation
0,00 s
2305 Autotune Run
Off
GROUP 24 TORQUE CONTROL
2401 Torq Ramp Up
0.00 s
2402 Torq Ramp Down
0.00 s
GROUP 25 CRITICAL SPEEDS
2501 Crit Speed Sel
Off
2502 Crit Speed 1 Lo
0.0 Hz
2503 Crit Speed 1 Hi
0.0 Hz
2504 Crit Speed 2 Lo
0.0 Hz
2505 Crit Speed 2 Hi
0.0 Hz
2506 Crit Speed 3 Lo
0.0 Hz
2507 Crit Speed 3 Hi
0.0 Hz
GROUP 26 MOTOR CONTROL
2601 Flux Opt Enable
On
2602 Flux Braking
Off
2603 IR Comp Volt
0 V
2604 IR Comp Freq
50%
2605 V/F Ratio
Square
2606 Switching Freq
4 kHz
2607 Switch Freq Ctrl
On
2608 Slip Comp Ratio
0%
GROUP 29 MAINTENANCE TRIG
2901 Cooling Fan Trig
0.0 kh
2902 Cooling Fan Act
0.0 kh
2903 Revolution Trig
0 Mrev
2904 Revolution Act
1 Mrev
2905 Run Time Trig
0.0 kh
2906 Run Time Act
0.0 kh
2907 User MWh Trig
0.0 MWh
2908 User MWh Act
0.0 MWh
GROUP 30 FAULT FUNCTIONS
3001 AI<Min Function
Not Sel
3002 Panel Comm Error
Fault
3003 External Fault 1
Not Sel
3004 External Fault 2
Not Sel
3005 Mot Therm Prot
Fault
3006 Mot Therm Time
1050 s
3007 Mot Load Curve
100%
3008 Zero Speed Load
70%
3009 Break Point
35 Hz
3010 Stall Function
Not Sel
3011 Stall Frequency
20.0 Hz
3012 Stall Time
20 s
3013 Underload Func
0
3014 Underload Time
20 s
3015 Underload Curve
1
3017 Earth Fault
Enable
3018 Comm Fault Func
Not Sel
3019 Comm Fault Time
10.0 s
3021 AI1 Fault Limit
0.0%
3022 AI2 Fault Limit
0.0%
GROUP 31 AUTOMATIC RESET
3101 NR of Trials
5
3102 Trial Time
30.0 s
3103 Delay Time
6.0 s
3104 AR Overcurrent
Disable
3105 AR Overvoltage
Enable
3106 AR Undervoltage
Enable
3107 AR AI<Min
Enable
3108 AR External Fit
Enable
GROUP 32 SUPERVISION
3201 Superv1 Param
Output Freq
3202 Superv1 Lim Lo
60.0 Hz
3203 Superv1 Lim Hi
60.0 Hz
3204 Superv2 Param
Current
3205 Superv2 Lim Lo
A
3206 Superv2 Lim Hi
A
3207 Superv3 Param
100.0%
3208 Superv3 Lim Lo
100.0%
3209 Superv3 Lim Hi
100.0%
GROUP 33 INFORMATION
3301 FW Version
141B hex
3302 LP Version
0000 hex
3303 Test Date
0.00
3304 Drive rating
hex
continued . . .
YORK Defaults