AYK550-UH User’s Manual
86
Start-Up
2207
RAMP SHAPE 2
0…1000.0 s
0.1 s
0.0
Selects the shape of the acceleration/deceleration ramp for ramp pair 2. See 2004
RAMP
SHAPE
1.
2208
EM DEC TIME
0.0…1800 s
0.1 s
1.0 s
Sets the deceleration time for maximum frequency to zero for an emergency.
• See parameter 2109
EM
STOP
SEL
.
• Ramp is linear.
2209
RAMP INPUT 0
-6…6
1
0
Defines control for forcing the ramp input to 0.
0 =
NOT
SEL
–
1 =
DI
1 – Defines digital input
DI
1 as the control for forcing the ramp input to 0.
• Activating the digital input forces ramp input to 0. Ramp output will ramp to 0 according to the currently used
ramp time, after which it will stay at 0.
• De-activating the digital input: ramp resumes normal operation.
2…6 =
DI
2…
DI
6 – Defines digital input
DI
2…
DI
6 as the control for forcing the ramp input to 0.
• See
DI
1 above.
-1 =
DI
1(
INV
) – Defines an inverted digital input
DI
1 as the control for forcing the ramp input to 0.
• De-activating the digital input forces ramp input to 0.
• Activating the digital input: ramp resumes normal operation.
-2…-6 =
DI
2(
INV
)…
DI
6(
INV
) – Defines an inverted digital input
DI
2…
DI
6 as the control for forcing the ramp function
generator input to 0.
• See
DI
1(
INV
) above.
Group 22: Accel/Decel
Code Description Range
Resolution
Default
S
Summary of Contents for AYK 550
Page 256: ...D1 AYK550 UH User s Manual Appendix D Appendix D Base Drive Drawing 205662 Drawings Fig 1...
Page 257: ...AYK550 UH User s Manual D2 Appendix D Base Drive w Fused Disconnect Drawing 205648 Fig 2...
Page 258: ...D3 AYK550 UH User s Manual Appendix D Base Drive w Non Fused Disconnect Drawing 205647 Fig 3...