AYK550-UH User’s Manual
181
Serial Communication – EFB
Point Database
The following table lists the point database for FLN / AYK550 (Application 2734).
FLN Point Database
Point
Subpoint Name
Factory
Default
Engr.
Units
Slope
Intercept
On Text
Off Text
#
Type
(SI Units)
01
LAO
CTLR ADDRESS 99
-
1
0
-
-
02
LAO
APPLICATION
2734
-
1
-
-
{03} LAI
FREQ OUTPUT
0
Hz
0.1
0
-
-
{04} LAI
PCT OUTPUT
0
PCT
0.1
0
-
-
{05} LAI
SPEED
0
RPM
1
0
-
-
{06} LAI
CURRENT
0
A
0.1
-
-
{07} LAI
TORQUE
0
PCT
0.1
-200
-
-
{08} LAI
POWER
0
(0)
HP
(KW)
0.134
0.1
0
0
-
-
{09} LAI
DRIVE TEMP
77
(25)
°
F
(
°
C)
0.18
(0.1)
32
0
-
-
{10} LAI
DRIVE KWH
0
KWH
1
-
-
{11}
LAI
DRIVE MWH
0
MWH
1
-
-
{12} LAI
RUN TIME
0
HRS
1
-
-
{13} LAI
DC BUS VOLT
0
V
1
-
-
{14} LAI
OUTPUT VOLT
0
V
1
-
-
{15} LAI
PRC PID FBCK
0
PCT
0.1
-
-
{16} LAI
PRC PID DEV
0
PCT
0.1
-
-
{17} LAI
MOTOR TEMP
77(25)
°
F (
°
C)
1.8 (1)
32 0
-
-
{18} LAI
MREV
COUNTER
0
MREV
1
0
-
-
20
LAO
OVRD TIME
1
hrs
1
0
-
-
{21} LDI
FWD.REV
FWD
-
1
0
REV
FWD
{22} LDO
CMD FWD.REV
FWD
-
1
0
REV
FWD
{23} LDI
STOP.RUN
STOP
-
1
0
RUN
STOP
{24} LDO
CMD STP.STRT
STOP
-
1
0
RUN
STOP
{25} LDI
EXT1.2 ACT
EXT1
-
1
0
EXT2
EXT1
{26} LDO
EXT1.2 CMD
EXT1
-
1
0
EXT2
EXT1
{27} LDI
DRIVE READY
NOTRDY -
1
0
READY
NOTRDY
{28} LDI
AT SETPOINT
NO
-
1
0
YES
NO
{29} LDO
DAY.NIGHT
DAY
-
1
0
NIGHT
DAY
30
LAO
CURRENT LIM
0
A
0.1
0
-
-
31
LAO
ACCEL TIME 1
300
sec
0.1
0
-
-
32
LAO
DECEL TIME 1
300
sec
0.1
0
-
-
{33} LDI
HANDAUTO
ACT
AUTO
-
1
0
HAND
AUTO