AYK550-UH User’s Manual
173
Serial Communication – EFB
N2 Binary Output Objects
The following table lists all of the N2 Binary Output objects defined for the AYK550
drive.
1. N2 LOCAL CTL and N2 LOCAL REF have priority over drive input terminals. Use these binary
outputs for temporary N2 control of the drive when
COMM
is not the selected control source.
DDL File for NCU
The listing below is the Data Definition Language (DDL) file for AYK550 drives used
with the Network Control Units.
This listing is useful when defining drive I/O objects to the Network Controller Units.
Below is the AYK550.DDL file listing.
*******************************************************************
* YORK Drives, AYK 550 Variable Frequency Drive
*******************************************************************
A020
MAILBOX DATA
1
0…65535
N2 Binary Outputs:
Number
Object
Drive Parameter
Range
BO1
STOP/START
Command Word
0 = Stop, 1 = Start to Speed
BO2
FORWARD/REVERSE
Command Word
0 = Forward, 1 = Reverse
BO3
PANEL LOCK
Command Word
0 = Open, 1 = Locked
BO4
RUN ENABLE
Command Word
0 = Enable, 1 = Disable
BO5
REF1/REF2 SELECT
Command Word
0 = Ref1, 1 = Ref2
BO6
FAULT RESET
Command Word
Change 0 -> 1 Resets
BO7
COMMAND RO 1
134 (bit mask 01)
0 = Off, 1 = On
BO8
COMMAND RO 2
134 (bit mask 02)
0 = Off, 1 = On
BO9
COMMAND RO 3
134 (bit mask 04)
0 = Off, 1 = On
BO10
COMMAND RO 4
134 (bit mask 08)
0 = Off, 1 = On
BO11
COMMAND RO 5
134 (bit mask 10)
0 = Off, 1 = On
BO12
COMMAND RO 6
134 (bit mask 20)
0 = Off, 1 = On
BO13
RESET RUN TIME
114 (indirectly)
0 = N/A, 1 = On (Reset Run Time)
BO14
RESET KWH COUNT
115 (indirectly)
0 = N/A, 1 = On (Reset kWh Count)
BO15
PRC PID SELECT
4027 (indirectly)
0 = SET2, 1 = SET2
BO16
N2 LOCAL CTL (Note 1)
Command Word
0 = Auto, 1 = N2
BO17
N2 LOCAL REF (Note 1) Command Word
0 = Auto, 1 = N2
BO18
SAVE PARAMETERS
1607 (indirectly)
0 = N/A, 1 = On (Save Parameters)
B019
READ MAILBOX
0 = No, 1 = Yes
B020
WRITE MAILBOX
0 = No, 1 = Yes
N2 Analog Outputs:
Number
Object
Drive
Parameter
Scale
Factor
Units
Range
Summary of Contents for AYK 550
Page 256: ...D1 AYK550 UH User s Manual Appendix D Appendix D Base Drive Drawing 205662 Drawings Fig 1...
Page 257: ...AYK550 UH User s Manual D2 Appendix D Base Drive w Fused Disconnect Drawing 205648 Fig 2...
Page 258: ...D3 AYK550 UH User s Manual Appendix D Base Drive w Non Fused Disconnect Drawing 205647 Fig 3...