Diagnostics
5
OVERLOAD
Inverter overload condition. The drive output current exceeds the ratings
given in "Ratings" on page 225.
6
DC
UNDERVOLT
Intermediate circuit DC voltage is not sufficient. Check for and correct:
• Missing phase in the input power supply.
• Blown fuse.
• Undervoltage on mains.
7
AI
1
LOSS
Analog input 1 loss. Analog input value is less than
AI
1
FLT
LIMIT
(3021).
Check for and correct:
• Source and connection for analog input.
• Parameter settings for
AI
1
FLT
LIMIT
(3021) and 3001
AI
<
MIN FUNCTION
.
8
AI
2
LOSS
Analog input 2 loss. Analog input value is less than
AI
2
FLT
LIMIT
(3022).
Check for and correct:
• Source and connection for analog input.
• Parameter settings for
AI
2
FLT
LIMIT
(3022) and 3001
AI
<
MIN FUNCTION
.
9
MOT
TEMP
Motor is too hot, based on either the drive’s estimate or on temperature
feedback.
• Check for overloaded motor.
• Adjust the parameters used for the estimate (3005…3009).
• Check the temperature sensors and Group 35 parameters.
10
PANEL
LOSS
Panel communication is lost and either:
• Drive is in local control mode (the control panel displays HAND), or
• Drive is in remote control mode (REM) and is parameterized to accept
start/stop, direction or reference from the control panel.
To correct check:
• Communication lines and connections
• Parameter 3002
PANEL
COMM
ERROR
.
• Parameters in Group 10: Command Inputs and Group 11: Reference
Select (if drive operation is REM).
11
ID
RUN
FAIL
The motor ID run was not completed successfully. Check for and correct:
• Motor connections
12
MOTOR
STALL
Motor or process stall. Motor is operating in the stall region. Check for and
correct:
• Excessive load.
• Insufficient motor power.
• Parameters 3010…3012.
13
R
ESERVED
Not used.
14
EXTNAL
FLT
1
Digital input defined to report first external fault is active. See parameter
3003
EXTERNAL
FAULT
1.
15
EXTERNAL
FLT
2 Digital input defined to report second external fault is active. See parameter
3004
EXTERNAL
FAULT
2.
16
EARTH
FAULT
The load on the input power system is out of balance.
• Check for/correct faults in the motor or motor cable.
• Verify that motor cable does not exceed max. specified length.
17
UNDERLOAD
Motor load is lower than expected. Check for and correct:
• Disconnected load.
• Parameters 3013
UNDERLOAD
FUNCTION
…3015
UNDERLOAD
CURVE
.
Fault
Code
Fault Name In
Panel
Description and Recommended Corrective Action