AYK550-UH User’s Manual
Installation
Note!
Before increasing motor speed, check that the motor is running in the desired
direction.To change rotation direction, switch motor leads as shown below.
Note!
For drives with bypass, if motor is running in reverse switch incoming power
lines at input disconnect.
Start-Up
The AYK550 has default parameter settings that are sufficient for many situations.
However, review the following situations. Perform the associated procedures as
appropriate.
Spin Motor
When first installed and started the control panel displays a welcome screen with the
following options.
• Press Exit to commission the drive as described in section “Start-Up by Changing
the Parameters Individually” on page 23.
• Press Enter to move to the following options:
– Select “Commission Drive” to commission the drive as described in section
“Start-Up by Using the Start-Up Assistant” on page 23.
– Select “Spin Motor” to operate the motor prior to commissioning. This option
operates the motor without any commissioning, except entry of the motor data
as described below. Spin Motor is useful, for example, to operate ventilation
fans prior to commissioning.
Note!
When using Spin Motor, the motor speed is limited to the range 1/3…2/3 of
maximum speed. Also, no interlocks are activated. Finally, once the drive is
commissioned, the welcome screen and this option no longer appear.
U1
V1
W1
U2
V2
W2
L1
L2
L3
Motor
Drive
Input
FM
U1
V1
W1
U2
V2
W2
L1
L2
L3
Motor
Drive
Input
To change rotation direction,
switch motor leads
GND
GND
GND
GND