Technical Data
Air Flow, 208…240 Volt Drives
The following table lists heat loss and air flow data for 208…240 Volt drives.
Dimensions and Weights
The dimensions and mass for the AYK550 depend on the frame size and enclosure
type. If unsure of frame size, first, find the “Type” code on the drive labels. Then look
up that type code in the "Technical Data" on page 221, to determine the frame size.
A complete set of dimensional drawings for AYK550 drives is located in the AYK550
Technical Reference manual.
-077A-4
R5
1295
4420
168
99
-096A-4
R5
1440
4915
168
99
-124A-4
R6
1940
6621
405
238
-157A-4
R6
2310
7884
405
238
-180A-4
R6
2810
9590
405
238
Drive
Heat Loss
Air Flow
AYK550-UH-
Frame Size
W
BTU/Hr
m
3
/h
ft
3
/min
-04A6-2
R1
55
189
44
26
-06A6-2
R1
73
249
44
26
-07A5-2
R1
81
276
44
26
-012A-2
R1
116
404
44
26
-017A-2
R1
161
551
44
26
-024A-2
R2
227
776
88
52
-031A-2
R2
285
373
88
52
-046A-2
R3
420
1434
134
79
-059A-2
R3
536
1829
134
79
-075A-2
R4
671
2290
280
165
-088A-2
R4
786
2685
280
165
-114A-2
R4
1014
3463
280
165
-143A-2
R6
1268
4431
405
238
-178A-2
R6
1575
5379
405
238
-221A-2
R6
1952
6666
405
238
-248A-2
R6
2189
7474
405
238
Drive
Heat Loss
Air Flow
AYK550-UH-
Frame Size
W
BTU/Hr
m
3
/h
ft
3
/min
Summary of Contents for AYK 550
Page 256: ...D1 AYK550 UH User s Manual Appendix D Appendix D Base Drive Drawing 205662 Drawings Fig 1...
Page 257: ...AYK550 UH User s Manual D2 Appendix D Base Drive w Fused Disconnect Drawing 205648 Fig 2...
Page 258: ...D3 AYK550 UH User s Manual Appendix D Base Drive w Non Fused Disconnect Drawing 205647 Fig 3...