a. Points not listed are not used in this application.
b. A single value in a column means that the value is the same in English units and in SI units.
c. Point numbers that appear in brackets { } may be unbundled at the field panel.
66
LDO
SPD OUT MIN
0
PCT
0.1
0
-
-
67
LDO
SPD OUT MAX
1000
PCT
0.1
0
-
-
{68} LDO
FLN LOC CTL
AUTO
-
1
0
FLN
AUTO
{69} LDO
FLN LOC REF
AUTO
-
1
0
FLN
AUTO
{70} LDI
DI 1 ACTUAL
OFF
-
1
0
ON
OFF
{71} LDI
DI 2 ACTUAL
OFF
-
1
0
ON
OFF
{72} LDI
DI 3 ACTUAL
OFF
-
1
0
ON
OFF
{73} LDI
DI 4 ACTUAL
OFF
-
1
0
ON
OFF
{74} LDI
DI 5 ACTUAL
OFF
-
1
0
ON
OFF
{75} LDI
DI 6 ACTUAL
OFF
-
1
0
ON
OFF
{76} LDI
RO 1 ACTUAL
OFF
-
1
0
ON
OFF
{77} LDI
RO 2 ACTUAL
OFF
-
1
0
ON
OFF
{78} LDI
RO 3 ACTUAL
OFF
-
1
0
ON
OFF
{79} LDI
RO 4 ACTUAL
OFF
-
1
0
ON
OFF
{80} LDI
RO 5 ACTUAL
OFF
-
1
0
ON
OFF
{81} LDI
RO 6 ACTUAL
OFF
-
1
0
ON
OFF
{82} LAI
AI 1 ACTUAL
0
PCT
0.1
0
-
-
{83} LAI
AI 2 ACTUAL
0
PCT
0.1
0
-
-
{84} LAI
AO 1 ACTUAL
0
MA
0.1
0
-
-
{85} LAI
AI 2 ACTUAL
0
MA
0.1
0
-
-
{86} LDI
OK.ALARM
OK
-
1
0
ALARM
OK
{87} LDI
OK.MAINT
OK
-
1
0
MAINT
OK
{88} LAI
ALARM WORD 1 -
-
1
0
-
-
{89} LAI
ALARM WORD 2 -
-
1
0
-
-
{90} LAI
LAST FAULT
-
-
1
0
-
-
{91} LAI
PREV FAULT 1
-
-
1
0
-
-
{92} LAI
PREV FAULT 2
-
-
1
0
-
-
{93} LDI
OK.FAULT
OK
-
1
0
FAULT
OK
{94} LDO
RESET FAULT
NO
-
1
0
RESET
NO
{95} LAO
MBOX PARAM
-
-
1
0
-
-
{96} LAO
MBOX DATA
-
-
1
0
-
-
{97} LDO
MBOX READ
DONE
-
1
0
READ
DONE
{98} LDO
MBOX WRITE
DONE
-
1
0
WRITE
DONE
{99} LAO
ERROR STATUS -
-
1
0
-
-
FLN Point Database
Point
Subpoint Name
Factory
Default
Engr.
Units
Slope
Intercept
On Text
Off Text
#
Type
(SI Units)