Object ID
Object Name
Modbus
Address
Precision
Range
Units
PV Access
AV8
Data Link Status (Bitmapped)
Bit 0: Writing Data
Bit 1: Reserved
Bit 2: Reserved
Bit 3: Upper or lower limit error
Bit 4: Data conformity error
Bit 5: Writing to EEPROM
Bit 6 to F: Reserved
0x0022
–
0 to 63
Bitmapped
R
AV9
Frequency Reference
0040H
XXX.XX
Depends on
o1-03
–
Hz
Depends on
o1-03
R
AV10
Output Frequency
0041H
XXX.XX
Depends on
o1-03
–
Hz
Depends on
o1-03
R
AV11
Output Voltage
0045H
XXXX.X
–
Volts
R
AV12
Output Current
0026H
XXXX.X
(for drives rated
above 11 kVA)
XXX.XX
(for drives rated
11 kVA or lower)
–
Amps
R
AV13
Output Power
0047H
XXXX.X
(for drives rated
above 11 kVA)
XXX.XX
(for drives rated
11 kVA or lower)
–
kW
R
AV14
Torque Reference
0048H
XXXX.X
–
%
R
AV15
MF Input Status
–
–
–
–
–
AV16
Drive Status 2
–
–
–
–
–
AV17
MF Output Status
–
–
–
–
–
AV18
DC Bus Voltage
0031H
XXXX.X
–
Volts
R
AV19
PI Feedback Level
0038H
XXXX.X
–
%
R
AV20
PI Input Level
0039H
XXXX.X
–
%
R
AV21
PI Output Level
003AH
XXXX.X
–
%
R
AV22
CPU Software
005BH
XXXXX
–
–
R
AV23
Flash Number
004DH
XXXXX
–
–
R
AV24
Not used
–
–
–
–
–
AV25
kVA Setting
0508H
XXXXX
–
–
R
AV26
Control Method
0043H
XXXXX
–
–
R
AV27
Accel Time
0200H
XXXX.X
(when C1-10 = 1)
XXX.XX
(when C1-10 = 0)
0.0 to 6000.0
(when C1-10 = 1)
0.00 to 600.00
(when C1-10 = 0)
Sec
W
AV28
Decel Time
0201H
XXXX.X
(when C1-10 = 1)
XXX.XX
(when C1-10 = 0)
0.0 to 6000.0
(when C1-10 = 1)
0.00 to 600.00
(when C1-10 = 0)
Sec
W
AV29
Param Number
–
XXXXX
0 to FFFFH
–
W
AV30
Param Data
–
XXXXX
0 to FFFFH
–
W
<1>
Refer to Accessing Drive Parameters and the Enter Command on page 358
for an explanation of how to read and write drive parameters not
listed in the analog or binary objects.
C.7 BACnet Objects Supported
YASKAWA ELECTRIC TOEP C710616 45F YASKAWA AC Drive – Z1000 User Manual
355
C
BACnet Communications