Property
Object Type
Device
Analog
Input
Analog
Output
Analog
Value
Binary
Output
Binary
Output
Binary
Value
Inactive_Text
–
–
–
–
Yes
Yes
Yes
Active_Text
–
–
–
–
Yes
Yes
Yes
<1> For Commandable Object Instances only.
u
Analog Input Objects
Table C.5 Analog Input Objects
Object ID
Object Name
Modbus
Address
Precision
Range
Units
PV Access
AI1
Analog Input 1 Level
004EH
XXXX.X
–
%
R
AI2
Analog Input 2 Level
004FH
XXXX.X
–
%
R
AI3
Not used
–
–
–
–
–
AI4
Not used
–
–
–
–
–
AI5
Not used
–
–
–
–
–
AI6
Display Format o1-03
0502H
XXXXX
–
–
R
AI7
Scale Format b5-20
01E2H
XXXXX
–
–
R
AI8
Inverter Model o2-04
0508F
XXXXX
–
–
R
AI9
Rated Current n9-01
05D0H
XXXX.X (for
drives rated
above 11 kVA)
XXX.X (for
drives rated 11
kVA or lower)
–
Amps
R
u
Analog Output Objects
Table C.6 Analog Output Objects
Object ID
Object Name
Modbus
Address
Precision
Range
Units
PV Access
AO1
Analog Output 1 Level
0007H
XXXX.X
0 to 100.0
%
C
AO2
Analog Output 2 Level
0008H
XXXX.X
0 to 100.0
%
C
u
Analog Value Objects
Table C.7 Analog Value Objects
Object ID
Object Name
Modbus
Address
Precision
Range
Units
PV Access
AV1
Operation Cmd (Bitmapped)
Bit 0: Run Fwd
Bit 1: Run Rev
Bit 2: External Fault (EF0)
Bit 3: Fault Reset
Bit 4: Multi-Function Input 1
(ComRef when H1-01 = 40)
Bit 5: Multi-Function Input 2
(ComCtrl when H1-02 = 41)
Bit 6: Multi-Function Input 3
Bit 7: Multi-Function Input 4
Bit 8: Multi-Function Input 5
Bit 9: Multi-Function Input 6
Bit A: Multi-Function Input 7
Bit B to F : Reserved
Note:
When using AV1, do not use
BV1 to BV11 or AV5.
0x0001
–
0 to 2047
Bitmapped
C
AV2
Frequency Command
0002H
XXX.XX
Depends on
o1-03
0.00 to 600.00
Hz
Depends on
o1-03
C
AV3
PI Setpoint
0006H
XXX.XX
0.00 to 100.00
%
C
C.7 BACnet Objects Supported
YASKAWA ELECTRIC TOEP C710616 45F YASKAWA AC Drive – Z1000 User Manual
353
C
BACnet Communications
Summary of Contents for Z1000 CIMR-ZU*A Series