HOA Keypad Display
Minor Fault Name
The motor is short-circuited
• Check the motor power cable, relay terminals and motor terminal box for short circuits.
• Correct grounding shorts and turn the power back on.
Ground current has overcharged the main circuit
capacitors via the drive input power
Noise interference causes the drive to operate
incorrectly
• Review possible solutions for handling noise interference.
• Review section on handling noise interference and check control circuit lines, main circuit lines
and ground wiring.
• If the magnetic contactor is identified as a source of noise, install a surge protector to the MC coil.
Set number of fault restarts (L5-01) to a value other than 0.
HOA Keypad Display
Minor Fault Name
PASS
MEMOBUS/Modbus Comm. Test Mode Complete
Cause
Possible Solutions
MEMOBUS/Modbus test has finished normally
This verifies that the test was successful.
HOA Keypad Display
Minor Fault Name
SAFE
Customer Safety
Customer Safeties mult-function input is open. This alarm has display priority over the Interlock Open
(inTLK).
Cause
Possible Solutions
External contact from customer wiring is open.
Check the cause of the open safety.
HOA Keypad Display
Minor Fault Name
SE
MEMOBUS/Modbus Communication Test Mode Error
Note:
This alarm will not trigger a multi-function output terminal that is set for alarm output
(H2-
oo
= 10).
Cause
Possible Solutions
A digital input set to 67H (MEMOBUS/Modbus
test) was closed while the drive was running
Stop the drive and run the test again.
HOA Keypad Display
Minor Fault Name
TrPC
IGBT Maintenance Time (90%)
IGBTs have reached 90% of their expected performance life.
Cause
Possible Solutions
IGBTs have reached 90% of their expected
performance life
Replace the drive.
HOA Keypad Display
Minor Fault Name
UL3
Undertorque Detection 1
Drive output current less than L6-02 for longer than L6-03 time.
Cause
Possible Solutions
Inappropriate parameter settings
Check parameters L6-02 and L6-03.
Load has dropped or decreased significantly
Check for broken parts in the transmission system.
HOA Keypad Display
Minor Fault Name
UL6
Undertorque Detection 6
Cause
Possible Solutions
The load has dropped or decreased under the motor
underload curve
Check parameters L6-13 and L6-14.
HOA Keypad Display
Minor Fault Name
Uv
Undervoltage
One of the following conditions was true when the drive was stopped and a Run command was
entered:
• DC bus voltage dropped below the level specified in L2-05.
• Contactor to suppress inrush current in the drive was opened.
• Low voltage in the control drive input power. This alarm outputs only if L2-01 is not 0 and DC
bus voltage is under L2-05.
5.5 Alarm Detection
YASKAWA ELECTRIC TOEP C710616 45F YASKAWA AC Drive – Z1000 User Manual
225
5
Troubleshooting