4.8 Auto-Tuning
u
Types of Auto-Tuning
The drive offers different types of Auto-Tuning for induction motors and permanent magnet motors. The type of Auto-Tuning
used differs further based on the control mode and other operating conditions. Refer to the tables below to select the type of
Auto-Tuning that bests suits the application.
Refer to Start-Up Flowcharts on page 119
for directions on executing Auto-
Tuning.
Note:
The drive will only show Auto-Tuning parameters that are valid for the control mode that has been set in A1-02. If the control mode is for
an induction motor, the Auto-Tuning parameters for PM motors will not be available.
n
Auto-Tuning for Induction Motors
This feature automatically sets the V/f pattern and motor parameters E1-
oo
and E2-
oo
for an induction motor.
Table 4.18 Types of Auto-Tuning for Induction Motors
Type
Setting
Application Conditions and Benefits
Control
Mode
V/f
Stationary Auto-Tuning for Line-
to-Line Resistance
T1-01 = 2
• The drive is used in V/f Control and other Auto-Tuning selections are not
possible.
• Drive and motor capacities differ.
• Tunes the drive after the cable between the drive and motor has been replaced
with a cable over 50 m long. Assumes Auto-Tuning has already been
performed.
• Should not be used for any vector control modes unless the motor cable has
changed.
YES
Rotational Auto-Tuning for V/f
Control
T1-01 = 3
• Recommended for applications using Speed Estimation Speed Search or using
the Energy Saving function in V/f Control.
• Assumes motor can rotate while Auto-Tuning is executed. Increases accuracy
for certain functions like torque compensation, slip compensation, Energy
Saving, and Speed Search.
YES
The necessary information is usually listed on the motor nameplate or in the motor test report provided by the motor
manufacturer. Also refer to page
for details on Auto-Tuning processes and selections.
Table 4.19 Auto-Tuning Input Data
Input Value
Input Parameter
Unit
Tuning Type (T1-01)
2
Line-to-Line Resistance
3
Rotational for
V/f Control
Motor rated power
T1-02
kW
YES
YES
Motor rated voltage
T1-03
Vac
–
YES
Motor rated current
T1-04
A
YES
YES
Motor rated frequency
T1-05
Hz
–
YES
Number of motor poles
T1-06
–
–
YES
Motor rated Speed
T1-07
r/min
–
YES
Motor iron loss
T1-11
W
–
YES
4.8 Auto-Tuning
YASKAWA ELECTRIC TOEP C710616 45F YASKAWA AC Drive – Z1000 User Manual
143
4
Start-Up Programming & Operation
Summary of Contents for Z1000 CIMR-ZU*A Series
Page 399: ......