-24
Connecting the Inverter and the D1000 Sine-Wave PWM Converter with Power Regeneration
* 1. The standard models of the Varispeed G7 Inverter can be connected to the D1000.
* 2. Never connect a power supply to the AC power supply terminals R/L1, S/L2, and T/L3 of the Varispeed G7 Inverter.
* 3. For Varispeed G7 200 V Class for 30 to 75 kW cooling fan terminals r/
1
and /
2
, disconnect the jumper wires between r/
1
- R/L1 and between
/
2
- S/L2, and then take the r/
1
and /
2
power supplies from the primary power supply line of the D1000. For 400 V Class for 55 to 160 kW
cooling fan terminals r/
1
and 400/
2
400, disconnect the jumper wires between r/
1
- R/L1 and between 400/
2
400 - S/L2, and then take the r/
1
and 400/
2
400 power supplies from the primary power supply line of the D1000.
* 4. Always use a specified AC reactor and harmonic filter module. The desired Inverter operation may not be possible if non-specified components are
used.
* 5. Use a sequence that operates the D1000 first and then the Varispeed G7 after the power supply is turned ON.
When the power supply is turned OFF, use a sequence that stops the Inverter, the motor, and the D1000 in that order.
Operating the Varispeed G7 without operating the D1000 or shutting down the power supply while the D1000 is operating may cause converter faults.
* 6. For information on the interlock with the Inverter, refer to
4.5 Operation with the Drive Connected
in the
Power Regenerative Converter YASKAWA
D1000 Series Instruction Manual (TOBP C710656 04)
.
* 7. For the 200 V Class CIMR-D5A2022 to D5A2075 and the 400 V Class CIMR-D5A4022 to D5A4160, this wiring was completed at the factory.
For the 200 V Class CIMR-D5A2015 and the 400 V Class CIMR-D5A4015, this wiring is not necessary.
r/
1
and /
2
in the diagram are the terminal names for 200 V Class for 37 to 75 kW Inverters. These terminal names differ by the D1000 capacity as
shown below.
•200 V Class for 22 kW and 400 V Class for 22 to 45 kW: /
2
, t/
3
(For the wiring, /
2
and 1/
21
are connected, and t/
3
and t1/
31
are con-
nected.)
•400 V Class for 75 and 160 kW: r/
1
, 400/
2
400
* 8. When installing a noise filter on the power supply side of the converter, install a reactor-type noise filter without a capacitor, such as a finemet zero-
phase reactor, behind the power supply-side ELCB. Do not install a filter with a built-in capacitor. The capacitor may overheat and become damaged
due to harmonic components.
* 9. The length of the wiring between the input AC reactor and the D1000 must not be more than 10 m.
* 10.The length of the DC bus wiring between the D1000 and the Inverter must not be more than 5 m.
D1000
+
-
Ground
S1
S2
S3
S4
S5
S6
S7
S8
SC
E(G)
MA
MB
MC
RUN-SB
External fault
Fault reset
(Reserved)
(Reserved)
(Reserved)
(Reserved)
(Reserved)
(Reserved)
External
Baseblock
Shield ground terminal
STOP
M1
M2
Converter
Fault relay output
250 Vac, max. 1 A
30 Vdc, max. 1 A
(min. 5 Vdc, 10 mA)
+V
A1
A2
A3
AC
R+
R-
S+
S-
IG
V
I
+24 V
MEMOBUS/
Modbus Communication
RS-422/RS-485
max. 115.2 kbps
Control Circuit
-V
Power supply
+10.5 Vdc, max. 20 mA
Power supply, -10.5 Vdc,
max. 20 mA
Analog Input 1
Analog Input 2
Analog Input 3
DIP Switch S1
Termination
resistor
(120 Ω, 1/2 W)
DIP Switch S2
FM
R/L1
S/L2
T/L3
CN5-A
CN5-B
CN5-C
S1 Forward Run / Stop
S2 Reverse Run / Stop
S3 External fault
S4 Fault reset
S5
S6
S7
S8
SC
Sequence common
Multi-function
digital inputs
Shield wire
connection terminal
E(G)
Varispeed G7
Drive
+
R/L1
1
S/L2
T/L3
-
A
B
IM
U/T1
V/T2
W/T3
Ground
Motor
0 V
AC
E(G)
AM
FM
AM
S9
S10
S11
S12
r1/
11
1/
21
t1/
31
Three-
Phase
Power
Supply
Input-side
AC reactor1
Harmonic Filter Module
U
V
W
X
Y
Z
ELCB
or
MCCB
X
Y
Z
R/L1
S/L2
T/L3
r
t
PC
P2
P1
r /
1
/
2
Multi-function
digital inputs
(default setting)
Multi-function analog
output 1
(Input Voltage)
0 to +10 Vdc
Multi-function analog
output 2
(Input Current)
0 to +10 Vdc
Multi-function
photocoupler output 1
(During MC on)
48 Vdc, max. 50 mA
Multi-function
photocoupler output 2
(Operation Ready)
48 Vdc, max. 50 mA
Multi-function relay
output (During Run 1)
250 Vac, max. 1 A
30 Vdc, max. 1 A
(min. 5 Vdc, 10 mA)
Option card
connectors
shielded line
twisted-pair shielded line
main circuit terminal
control circuit terminal
-
+
-
+
*8
*7
*4
*4, *9
*10, *11
*10, *11
*2
*3
*1
*5
*6