User Constant Tables
5-
101
* 1. The carrier frequency is as follows depending on the C6-02 setting.
1: 2.0 kHz, 2: 5.0 kHz, 3: 8.0 kHz, 4: 10.0 kHz, 5: 12.5 kHz, 6: 15.0 kHz, F: User setting (initial value for 400 V, 90 kW and 110 kW: 3.0 kHz)
* 2. C6-04 (Carrier Frequency Lower Limit) can be set only in V/f control and V/f control with PG modes.
* 3. Applicable for G7-Series Inverters with software versions PRG 1042 and later.
Con-
stant
Num-
ber
Name
Unit
Factory Setting
–
Inverter Capacity
kW
75
90
110
132
160
185
220
300
o2-04
kVA Selection
1
30
31
32
33
34
35
36
37
C6-02
*1
Carrier
frequency
selection
V/f
Factory setting
–
2
F
F
1
1
1
1
1
Maximum
setting
–
2
1
1
1
1
1
1
1
V/f with
PG
Factory setting
–
2
F
F
1
1
1
1
1
Maximum
setting
–
2
1
1
1
1
1
1
1
Open-
loop
vector
Factory setting
–
2
F
F
1
1
1
1
1
Maximum
setting
–
2
1
1
1
1
1
1
1
Flux
vector
Factory setting
–
1
F
*3
F
*3
F
*3
F
*3
F
*3
F
*3
1
Maximum
setting
–
2
1
1
1
1
1
1
1
C6-03
(C6-04)
*2
Carrier
frequency
upper limit
(carrier
frequency
lower limit)
V/f
Factory setting
kHz
5.0
3.0
3.0
2.0
2.0
2.0
2.0
2.0
Setting range
kHz
0.4 to
5.0
0.4 to
3.0
0.4 to
3.0
0.4 to
2.0
0.4 to
2.0
0.4 to
2.0
0.4 to
2.0
0.4 to
2.0
V/f with
PG
Factory setting
kHz
5.0
3.0
3.0
2.0
2.0
2.0
2.0
2.0
Setting range
kHz
0.4 to
5.0
0.4 to
3.0
0.4 to
3.0
0.4 to
2.0
0.4 to
2.0
0.4 to
2.0
0.4 to
2.0
0.4 to
2.0
Open-
loop
vector
Factory setting
kHz
5.0
3.0
3.0
2.0
2.0
2.0
2.0
2.0
Setting range
kHz
2.0 to
5.0
2.0 to
3.0
2.0 to
3.0
2.0 to
2.0
2.0 to
2.0
2.0 to
2.0
2.0 to
2.0
2.0 to
2.0
Flux
vector
Factory setting
kHz
2.0
1.5
*3
1.5
*3
1.5
*3
1.5
*3
1.5
*3
1.5
*3
2.0
Setting range
kHz
2.0 to
5.0
1.5 to
3.0
*3
1.5 to
3.0
*3
1.5 to
2.0
*3
1.5 to
2.0
*3
1.5 to
2.0
*3
1.5 to
2.0
*3
2.0 to
2.0
TOE-S616-60.1.book 101 ページ 2017年8月4日 金曜日 午後3時41分