5
-56
* The CH1 output can be adjusted when the H4-02 or H4-03 setting is displayed in Quick, Advanced, or Verify mode while the motor is stopped.
The CH2 output can be adjusted when the H4-05 or H4-06 setting is displayed in Quick, Advanced, or Verify mode while the motor is stopped.
For analog output, the value equivalent to 100% of output value of monitored item is multiplied by the gain setting and the set bias is added.
MEMOBUS Communications: H5
User constants for MEMOBUS communications are shown in the following table.
H4-08
Analog out-
put 2 signal
level selec-
tion
Sets the signal output level for
multi-function output 2 (termi-
nal AM)
0: 0 to +10 V output
1: -10 to 10 V output
0 or 1
0
No
A
A
A
A
A
424H
–
AO Level
Select2
Con-
stant
Number
Name
Description
Setting
Range
Factory
Setting
Change
during
Opera-
tion
Control Methods
MEMO-
BUS
Regis-
ter
Page
Display
V/f
V/f
with
PG
Open
Loop
Vec-
tor
1
Flux
Vec-
tor
Open
Loop
Vec-
tor
2
H5-01
Slave
address
Set the Inverter's slave address.
0 to 20
*1
1F
No
A
A
A
A
A
425H
6-95
Serial
Comm Adr
H5-02
Communi-
cation
speed
selection
Set the baud rate for MEMO-
BUS communications of com-
munications connection
terminals.
0: 1200 bps
1: 2400 bps
2: 4800 bps
3: 9600 bps
4: 19200 bps
0 to 4
3
No
A
A
A
A
A
426H
6-95
Serial Baud
Rate
H5-03
Communi-
cation par-
ity selection
Set the parity for MEMOBUS
communications of communi-
cations connection terminals.
0: No parity
1: Even parity
2: Odd parity
0 to 2
0
No
A
A
A
A
A
427H
6-95
Serial Com
Sel
H5-04
Stopping
method
after com-
munication
error
Set the stopping method for
communications errors.
0: Deceleration to stop using
deceleration time in C1-02
1: Coast to stop
2: Emergency stop using
deceleration time in C1-09
3: Continue operation
0 to 3
3
No
A
A
A
A
A
428H
6-95
Serial Fault
Sel
H5-05
Communi-
cation error
detection
selection
Set whether or not a communi-
cations timeout is to be
detected as a communications
error.
0: Do not detect.
1: Detect
0 or 1
1
No
A
A
A
A
A
429H
6-95
Serial Flt
Dtct
H5-06
Send wait
time
Set the time from the Inverter
receiving data to when the
Inverter starts to send.
5 to 65
5 ms
No
A
A
A
A
A
42AH 6-95
Transmit
WaitTIM
Con-
stant
Number
Name
Description
Setting
Range
Factory
Setting
Change
during
Opera-
tion
Control Methods
MEMO-
BUS
Regis-
ter
Page
Display
V/f
V/f
with
PG
Open
Loop
Vec-
tor
1
Flux
Vec-
tor
Open
Loop
Vec-
tor
2