2
-8
Connection Diagram
The connection diagram of the Inverter is shown in
Fig 2.2
. When using the Digital Operator, the motor
can be operated by wiring only the main circuits.
Note: The wiring of the main circuit depends on the Inverter capacity. Refer to page 2-20 for details.
* 1. Wiring sequence should shut off power to the drive when a fault output is triggered. For a 400 V Class power supply, install a step-down transformer.
* 2. Note that the Inverter is set to trigger a fault output whenever the fault restart function is activated (L5-02 = 1), then a sequence to interrupt power when
a fault occurs will result in shutting off the power to the Inverter as the Inverter attempts to restart itself.
The factory setting for L5-02 is 0 (fault output not active during restart attempt).
Fig 2.2 Connection Diagram (Model CIMR-G7A2018 Shown Above)
Inverter
CIMR-G7A2018
P2
PC
Open collector 1
Open collector 2
Open collector 3
Open collector 4
Multi-function
open-collector outputs
48 VDC 50 mA max.
P1
Default: Frequency
agree signal
Default: Zero
speed
MA
MC
MB
Fault output
*2
250 VAC, 10 mA min.
1 A max.
30 VAC, 10 mA min.
1 A max.
M1
M2
Multi-function contact oputput
250 VAC, 10 mA min. 1 A max.
30 VAC, 10 mA min. 1 A max.
Default: Running
signal
AC
MP
Pulse train output
Default: Output
frequency
3-phase power
200 to 240 V
50/60 Hz
R/L1
S/L2
T/L3
1MCCB
T
S
R
S5
S8
S9
(Main speed switching)
External
baseblock command
Multi-step speed
reference 3
Multi-step speed
reference 4
Acc/dec time 1
Emergency stop (
N
O)
S1
S2
S3
S4
Forward Run/Stop
Reverse Run/Stop
External fault
Fault reset
Multi-step speed reference 1
contact inputs
Multi-function
Factory
settings
IG
MEMOBUS
communications
RS-485/422
R+
R-
S-
S+
((
Braking Unit
(optional)
+ 1
+ 3
FM
AM
Multi-function analog output 1
AC
FM
E(G)
-10 to 10 V 2 mA
Default: Output frequency
0 to +10 V
Default: Output current
0 to +10 V
-10 to 10 V 2 mA
Multi-function analog output 2
Ammeter adjustment
20 k
Ω
SC
E (G)
Shield wire
connection terminal
P4
C4
P3
Factory setting:
minor fault
Factory setting:
Inverter operation
ready
S6
S7
Multi-step speed
reference 2
Jog frequency
selection
S11
S12
C
N
5 (
N
P
N
setting)
+24V 8mA
+24V
S10
P
P
4 to 20 mA
0 to 10 V
0 to 10 V
Pulse train input
RP
+V
A2
A3
AC
0V
Master speed
pulse train
Frequency setting power
Master speed reference
Multi-function anlog input
Master speed reference
4 to 20 mA (250
Ω
)
[0 to 10 V (20 k
Ω
) input]
+15 V, 20 mA
0 to 10 V (20 k
Ω
)
0 to 10 V (20 k
Ω
)
Frequency
Frequency setting
adjustment
setter
External
frequency
references
2
1
3
P
P
-V
(15V 20mA)
Terminating
resistance
C3
Factory setting:
Auxiliary frequency
reference
PG
PG-B2
TA1
1
2
3
4
5
6
(optional)
TA3
TA2
1
Pulse monitor output
30 mA max.
W
iring distance:
d
:
30 m max.
Shieded twisted-pair
wires
H
B
G
A
F
C
D
U
U/T1
V/T2
W
/T3
IM
(Ground to 100
Ω
max.)
V
W
IM
FU
FV
F
W
FU
FV
F
W
2MCCB
MC
Cooling fan
Motor
SA
2MCCB
Inverter fault output
*1
THRX
OFF
O
N
MC
MC
SA
THRX
2
1
2
1
SA
TRX
TRX
MC
C
MC
Fault contact
MA
Thermal relay
trip contact
for motor cooling fan
A
MA
C
MC
for Braking Unit
-
Level
detector
-
-
+
0
0
B
P
Braking Resistor Unit
(optional)
4
3
2
1
+
Thermal switch contact
Thermal relay trip contact
for Braking Resistor Unit
0 to 32 kHz (3 k
Ω
)
High level: 3.5 to 13.2 V input
0 to 32 kHz (2.2 k
Ω
)
2 k
Ω
2 k
Ω
Thermal relay trip contact
Thermal switch contact
A1
Pulse A
Pulse B
1
2
3
3
4
4
Ammeter adjustment
20 k
Ω
AM
Min. load
5 VDC, 10 mA
Min. load
5 VDC, 10 mA
TOE-S616-60.1.book 8 ページ 2017年8月4日 金曜日 午後3時41分