Protective and Diagnostic Functions
7-
19
CE
(blinking)
MEMOBUS
Com Err
MEMOBUS Communications Error
Normal reception was not possible for
2 s or longer after received control
data.
–
Check the communications devices
and signals.
BUS
(blinking)
Option
Com Err
Option Board Communications
Error
A communications error occurred in a
mode where the Run Command or a
frequency reference is set from an
Communications Option Board.
–
Check the communications devices
and signals.
CALL
(blinking)
Com Call
Communications on Standby
Control data was not normally
received when power was turned ON.
–
Check the communications devices
and signals.
RUNC
(blinking)
Ext Run
Active
Reset during Run Command Input
Error
The reset signal was input during Run
Command input from an external ter-
minal or other source.
–
Check that a Run Command is not
being input from an external termi-
nal or other source.
E5
(blinking)
SI-T WDT
Err
SI-T Watchdog Error Detected
A Watchdog error was detected when
the Run Command or a frequency ref-
erence was set from an option board
and continuous operation was set for
the E5 operation selection.
Synchronization error between master
controller and Inverter for control
data.
Check the communications timing
such as communications cycle.
*1
AER
(blinking)
SI-T
Address
Err
SI-T Station Number Setting Error
Station number of SI-T option board
was out of setting range.
Station number setting error.
Check the setting of the station
number.
*1
Circuit of SI-T option board is faulty.
Check the communications devices
and signals.
*1
CYC
(blinking)
SI-T Cycle
Err
SI-T Communications Cycle Set-
ting Error
Communications cycle of SI-T option
board was out of range.
Communications cycle of SI-T option
board set in master controller was out
of range.
Check the communication cycle of
SI-T option board set in master con-
troller.
*1
BB
(blinking)
Baseblock
Receiving External Baseblock
Command
An external baseblock signal was
input from a multi-function input ter-
minal, and the Inverter output was
shut down.
An external baseblock signal was
input from a multi-function input ter-
minal.
Check the external sequence.
HCA
(blinking)
High Cur-
rent Alarm
Current Alarm
The output current has exceeded the
overcurrent alarm level (over 150% of
the rated current).
The load is too heavy or the accel/
decel time is too short.
Increase the acceleration/decelera-
tion time.
Either a specialized motor or an
excessively large motor is being used.
Verify the setting for the Inverter
capacity.
The current has risen too high while
performing speed search either during
a momentary loss in power or during
a fault restart.
Momentary losses in power or fault
restarts may occasionally trigger an
overcurrent alarm, and are not nec-
essarily indicators of an overcurrent
problem.
Table 7.3 Alarm Displays and Processing (Continued)
Display
Meaning
Probable causes
Corrective Actions