5
-68
L8-05
Input open-
phase protec-
tion selection
0: Disabled
1: Enabled (Detects if input
current open-phase, power
supply voltage imbalance
or main circuit
electrostatic capacitor
deterioration occurs.)
This fault is detected if a load
is greater than approximately
80% of the maximum motor
capacity.
0 or 1
0
No
A
A
A
A
A
4B1H
–
Ph Loss In
Sel
L8-07
Output open-
phase protec-
tion selection
0: Disabled
1: Enabled
2: Enabled
Output open-phase is detected
at less than 5% of Inverter
rated current.
When applied motor capacity
is small for Inverter capacity,
output open-phase may be
detected inadvertently or
open-phase may not be
detected. In this case, set to 0.
0 to 2
0
No
A
A
A
A
A
4B3H
–
Ph Loss Out
Sel
L8-09
Ground pro-
tection
selection
0: Disabled
1: Enabled
0 or 1
1
No
A
A
A
A
A
4B5H
–
Ground Fault
Sel
L8-10
Cooling fan
control
selection
Set the ON/OFF control for
the cooling fan.
0: ON only when Inverter is
ON
1: ON whenever power is
ON
0 or 1
0
No
A
A
A
A
A
4B6H
–
FAN Control
Sel
L8-11
Cooling fan
control delay
time
Set the time in seconds to
delay turning OFF the cooling
fan after the cooling fan OFF
command is received.
0 to
300
60 s
No
A
A
A
A
A
4B7H
–
FAN OFF
TIM
L8-12
Ambient
temperature
Set the ambient temperature.
If set to 60
°
C, the Inverter
overload protection function
(OL2) will start 20% earlier.
45 to
60
45
°
C
No
A
A
A
A
A
4B8H
–
temp
L8-15
OL2 charac-
teristics
selection at
low speeds
0: OL2 characteristics at low
speeds disabled.
1: OL2 characteristics at
low speeds enabled.
0 or 1
1
No
A
A
A
A
A
4BBH
–
OL2
Chara@L-
Spd
L8-18
Soft CLA
selection
0: Disable (gain = 0)
1: Enable
0 or 1
1
No
A
A
A
A
A
4BEH
–
Soft CLA Sel
Con-
stant
Number
Name
Description
Setting
Range
Factory
Setting
Change
during
Opera-
tion
Control Methods
MEMO-
BUS
Regis-
ter
Page
Display
V/f
V/f
with
PG
Open
Loop
Vec-
tor
1
Flux
Vec-
tor
Open
Loop
Vec-
tor
2
TOE-S616-60.1.book 68 ページ 2017年8月4日 金曜日 午後3時41分