User Constant Tables
5-
79
U: Monitor Constants
The following settings are made with the monitor constants (U constants): Setting constants for monitoring in
drive mode.
Status Monitor Constants: U1
The constants used for monitoring status are listed in the following table.
* 1. The unit is set in o1-03 (frequency units of reference setting and monitor).
* 2. The unit differs according to the Inverter capacity. (The unit is 0.01 A for an Inverter capacity of 0.4 to 7.5 kW, and 0.1 A for an Inverter capacity of
11 kW and larger.)
Con-
stant
Number
Name
Description
Output Signal Level
During Multi-Function
Analog Output
Min.
Unit
Control Methods
MEMO-
BUS
Regis-
ter
Display
V/f
V/f
with
PG
Open
Loop
Vec-
tor
1
Flux
Vec-
tor
Open
Loop
Vec-
tor
2
U1-01
Frequency
reference
Monitors/sets the fre-
quency reference value.
*1
10 V: Max. frequency
(-10 to 10 V possible)
0.01
Hz
A
A
A
A
A
40H
Frequency
Ref
U1-02
Output
frequency
Monitors the output fre-
quency.
*1
10 V: Max. frequency
(-10 to 10 V possible)
0.01
Hz
A
A
A
A
A
41H
Output Freq
U1-03
Output
current
Monitors the output cur-
rent.
10 V: Inverter rated output
current
(0 to +10 V, absolute value
output)
0.01
A
*2
A
A
A
A
A
42H
Output
Current
U1-04
Control
method
Checks the current control
method.
(Cannot be output.)
–
A
A
A
A
A
43H
Control
Method
U1-05
Motor speed Monitors the detected
motor speed.
*1
10 V: Max. frequency
(-10 to 10 V possible)
0.01
Hz
No
A
A
A
A
44H
Motor Speed
U1-06
Output
voltage
Monitors the output volt-
age reference value in the
Inverter.
10 V: 200 VAC (400 VAC)
(0 to +10 V output)
0.1 V
A
A
A
A
A
45H
Output
Voltage
U1-07
DC bus
voltage
Monitors the main DC
voltage in the Inverter.
10 V: 400 VDC (800 VDC)
(0 to +10 V output)
1 V
A
A
A
A
A
46H
DC Bus
Voltage
U1-08
Output
power
Monitors the output power
(internally detected value).
10 V: Inverter capacity for
V/f control
Motor capacity (E2-
11) for vector control
(-10 to 10 V possible)
0.1
kW
A
A
A
A
A
47H
Output
kWatts
U1-09
Torque
reference
Monitor in internal torque
reference value for vector
control.
10 V: Motor rated torque
(-10 to 10 V possible)
0.1%
No
No
A
A
A
48H
Torque
Reference