10
-32
Using Contact and Open Collector Outputs
This example shows wiring for contact outputs and open collector outputs.
The following example is for the CIMR-G7A25P5 (200 V Class Inverter for 5.5 kW).
Fig 10.21
Inverter
U/T1
V/T2
W/T3
IM
Ground
MA
MB
MC
Error contact output
P2
PC
Open collector 1
Multi-function
open collector output
48 VDC 50 mA max.
P1
(Default: zero speed)
M1
M2
Multi-function contact output
(Default: RUN)
T/L3
S/L2
R/L1
3-phase power
T
S
R
FM
AM
Multi-function analog output 1
AC
E(G)
-10 to +10 V 2 mA
AM
FM
㸩
㸩
㸫
㸫
Default: Output frequency,
0 to +10 V
Default: Ouput current,
0 to +10 V
-10 to +10 V 2 mA
Multi-function analog output 2
Frequency meter scale adjustment resistor
20 k
Ȑ
B2
B1
Ammeter scale adjustment resistor
20 k
Ȑ
Motor
Sequence external power
supply
Surge
absorber
250 VAC max.
30 VDC max.
Flywheel
diode
48 VDC max.
48 VDC max.
Sequence
(Default: Freq agree)
250 VAC, 10 mA min. 1 A max.
30 VDC, 10 mA min. 1 A max.
250 VAC, 10 mA min. 1 A max.
30 VDC, 10 mA min. 1 A max.
E(G)
+ 1
+ 2
-
Flywheel
diode
Flywheel
diode
Open collector 2
Ground Fault Interrupter or
Molded-case Circuit Breaker