Acceleration and Deceleration Characteristics
6-
25
Preventing Overvoltage During Deceleration (Stall Prevention During
Deceleration Function)
The Stall Prevention During Deceleration function makes the rate of deceleration more gentle to suppress
increases in DC bus voltage when the DC bus voltage exceeds the set value during motor deceleration.
This function automatically lengthens the deceleration time with respect to the bus voltage, even if the decel-
eration time has been set to a considerably small value.
If L3-04 is set to 1 or 2, when the main circuit DC voltage approaches the stall prevention level during decel-
eration, deceleration stops, and when deceleration falls below the level, is restarted. Using this operation,
deceleration time is automatically lengthened. If L3-04 is set to 1, deceleration time returns to the set value,
and if L3-04 is set to 2, deceleration is automatically adjusted to a faster deceleration time within the range of
the stall prevention level during deceleration.
Related Constants
* The setting range for flux vector and open-loop vector 2 controls is 0 to 2.
Con-
stant
Number
Name
Description
Setting
Range
Factory
Setting
Change
during
Opera-
tion
Control Methods
MEMO
BUS
Regis-
ter
Display
V/f
V/f
with
PG
Open
Loop
Vector
1
Flux
Vec-
tor
Open
Loop
Vector
2
L3-04
Stall preven-
tion selection
during decel
0: Disabled (Deceleration as set.
If deceleration time is too
short, a main circuit
overvoltage may result.)
1: Enabled (Deceleration is
stopped when the main circuit
voltage exceeds the
overvoltage level.
Deceleration restarts when
voltage is returned.)
2: Intelligent deceleration mode
(Deceleration rate is
automatically adjusted so that
the Inverter can decelerate in
the shortest possible time. Set
deceleration time is
disregarded.)
3: Enabled (with Braking
Resistor Unit)
When a braking option (Braking
Resistor, Braking Resistor Unit,
Braking Unit) is used, always set
to 0 or 3.
0 to 3
*
1
No
Q
Q
Q
Q
Q
492H
StallP Decel Sel