* 7. The setting range for open-loop vector 2 control is 0 to 66.0 (0 to 132.0 for
PRG 103
).
For the 400 V Class, there are limitations on the maximum output frequency depending on the setting for the carrier frequency and capacity.
The maximum output frequency for 400 V, 90 to 110 kW is 250 Hz. The maximum output frequency for 400 V, 132 to 300 kW is 166 Hz.
* 8. The same capacity as that of the Inverter will be set if the constants are initialized.
* 9. The setting range for flux vector and open-loop vector 2 control is 0 to 2.
* 10.0 or 1 for flux vector control and open-loop vector 2 control.
* 11.The setting range depends on the capacity of the Inverter. The values for a 200 V Class Inverter for 0.4 kW are given.
* 12.Displayed in Quick Programming Mode when motor 2 is set for a multi-function input.
* 13.This setting is for software versions PRG 1040 and later. The factory setting with software versions PRG 1039 and earlier depends on the Inverter
capacity.