B.3 Parameter Table
YASKAWA ELECTRIC
SIEP C710606 44B YASKAWA AC Drive T1000V Technical Manual
321
Pa
ra
met
er
Li
st
B
◆
b: Application
Application parameters configure the Run Command Source, DC Injection Braking, Speed Search, Timer functions, PID
control, the Dwell function, Energy Savings and a variety of other application-related settings.
No.
Name
Description
Range
Def.
Control
Mode
Addr.
Hex
Pg.
V/f OL
V
P
M
b1: Operation Mode Selection
Use b1 parameters to configure the operation mode.
b1-01
Frequency Reference
Source 1
Selects the frequency reference input source.
0: Operator - Digital preset speed d1-01 to d1-08, d1-17.
1: Terminals - Analog input terminal A1 or A2.
2: MEMOBUS communications
3: Option PCB
4: Pulse Input (Terminal RP)
0 to 4
1
S S S
180
b1-02
Run Command Source 1
Selects the run command input source.
0: Operator - RUN and STOP keys on the digital operator.
1: Digital input terminals
2: MEMOBUS communications
3: Option PCB.
0 to 3
1
S S S
181
b1-03
Stopping Method Selection
Selects the stopping method when the run command is
removed.
0: Ramp to Stop
1: Coast to Stop
2: DC Injection Braking to Stop
3: Coast with Timer
(A new run command is ignored if received before the
timer expires)
0 to 3
0
S S S
182
DC Injection Braking at Stop cannot be
selected when using Open Loop Vector for
PM motors.
b1-04
Reverse Operation Selection
Permits or prohibits reverse operation.
0: Reverse enabled.
1: Reverse disabled.
0,1
0
A A A
183
b1-07
LOCAL/REMOTE Run
Selection
Determines the operation when the Run command source is
switched from LOCAL to REMOTE or between Run
source 1 and 2 while an external Run command is active at
the new source.
0: External Run command has to be cycled at the new
source to be activated.
1: External Run command at new source is accepted
immediately.
0,1
0
A A A
186
b1-08
Run Command Selection
while in Programming
Mode
0: Run command accepted only in the operation menu.
1: Run command accepted in all menus.
2: Prohibit entering Programming Mode during Run
0 to 2
0
A A A
187
b1-14
Phase Order Selection
Sets the phase order for drive output terminals U/T1, V/T2
and W/T3.
0: Standard
1: Switch phase order
0,1
0
A A A
1C3
b1-15
Frequency Reference
Source 2
Selects the frequency reference input source.
0: Operator - Digital preset speed d1-01 to d1-08, d1-17.
1: Terminals - Analog input terminal A1 or A2
2: MEMOBUS communications
3: Option PCB
4: Pulse Input (Terminal RP)
0 to 4
0
A A A
1C4
b1-16
Run Command Source 2
Selects the run command input source.
0: Operator - RUN and STOP keys on the digital operator.
1: Digital input terminals
2: MEMOBUS communications
3: Option PCB
0 to 3
0
A A A
1C5
b1-17
Run Command at Power Up
Determines the operation when a Run command is active at
power up of the drive.
0: Run command not issued, needs to be cycled
1: Run command issued, motor operation start
0,1
0
A A A
1C6