B.3 Parameter Table
YASKAWA ELECTRIC
SIEP C710606 44B YASKAWA AC Drive T1000V Technical Manual
329
Pa
ra
met
er
Li
st
B
◆
d: References
Reference parameters are used to set the various frequency reference values during operation.
No.
<10> Default setting value is dependent on parameter o1-03, Digital Operator Display Selection.
<13> Range upper limit is dependent on parameters E1-04, Maximum Output Frequency, and d2-01, Frequency Reference Upper Limit.
<15> Parameter can be changed during run.
Name
Description
Range
Def.
Control
Mode
Addr.
Hex
Pg.
V/f OL
V
P
M
d1: Frequency Reference
Use d1 parameters to configure the drive frequency reference.
d1-01
Frequency Reference 1
Frequency reference
0.00 to
400.00 Hz
0.00
Hz
S S S
280
d1-02
Frequency Reference 2
Frequency reference when digital input “Multi-Step Speed
Reference 1” (H1-
= 3) is on.
0.00
Hz
S S S
281
d1-03
Frequency Reference 3
Frequency reference when digital input “Multi-Step Speed
Reference 2” (H1-
= 4) is on.
0.00
Hz
S S S
282
d1-04
Frequency Reference 4
Frequency reference when digital inputs “Multi-Step Speed
Reference 1, 2” (H1-
= 3 and 4) are on.
0.00
Hz
S S S
283
d1-05
Frequency Reference 5
Frequency reference when digital input “Multi-Step Speed
Reference 3” (H1-
= 5) is on.
0.00
Hz
A A A
284
d1-06
Frequency Reference 6
Frequency reference when digital inputs “Multi-Step Speed
Reference 1, 3” (H1-
= 3 and 5) are on.
0.00
Hz
A A A
285
d1-07
Frequency Reference 7
Frequency reference when digital inputs “Multi-Step Speed
Reference 2, 3” (H1-
= 4 and 5) are on.
0.00
Hz
A A A
286
d1-08
Frequency Reference 8
Frequency reference when multi-function input “Multi-Step
speed reference 1, 2, 3” (H1-
= 3, 4, 5) are on.
0.00
Hz
A A A
287
d1-17
Jog Frequency Reference
Frequency reference when digital inputs “Jog Frequency
Reference”, “Forward Jog” or “Reverse Jog” are on. “Jog
Frequency Reference” has priority over “Multi-Step Speed
Reference 1 to 8”.
6.00
Hz
S S S
292
d2: Frequency Upper and Lower Limits
Use d2 parameters to configure the frequency reference limits.
d2-01
Frequency Reference
Upper Limit
Sets the frequency reference upper limit as a percentage of
maximum output frequency (E1-04). Output speed is limited
to this value even if the frequency reference is higher. This
limit applies to all frequency reference sources.
0.0 to
110.0
100.0
%
A A A
289
d2-02
Frequency Reference
Lower Limit
Sets the frequency reference lower limit as a percentage of
maximum output frequency (E1-04). Output speed is limited
to this value even if the frequency reference is lower. This
limit applies to all frequency reference sources.
0.0 to
110.0
0.0% A A A
28A
d2-03
Master Speed Reference
Lower Limit
Sets the minimum frequency reference lower limit if the
frequency reference is input using an analog input. Set as a
percentage of maximum output frequency (E1-04). The
higher of both values d2-02 and d2-03 will be the lower limit.
0.0 to
110.0
0.0% A A A
293
d2-04
Frequency Reference 2
Upper Limit
Sets the frequency reference 2 upper limit as a percentage of
maximum output frequency (E1-04). Output speed is limited
to this value even if the frequency reference 2 is higher. This
limit applies to all frequency reference sources.
0.0 to
110.0
100.0
%
A A A
2A8
d2-05
Frequency Reference 2
Lower Limit
Sets the frequency reference 2 lower limit as a percentage of
maximum output frequency (E1-04). Output speed is limited
to this value even if the frequency reference 2 is lower. This
limit applies to all frequency reference sources.
0.0 to
110.0
0.0% A A A
2A9
d7: Offset Frequency
Use d7 parameters to set the offset frequency.
d7-01
Offset Frequency 1
Added to the frequency reference when the digital input
“Frequency Offset 1” (H1-
= 44) is switched on.
-100.0 to
+100.0
0.0% A A A
2B2
d7-02
Offset Frequency 2
Added to the frequency reference when the digital input
“Frequency Offset 2” (H1-
= 45) is switched on.
-100.0 to
+100.0
0.0% A A A
2B3
d7-03
Offset Frequency 3
Added to the frequency reference when the digital input
“Frequency Offset 3” (H1-
= 46) is switched on.
-100.0 to
+100.0
0.0% A A A
2B4