
5.10 o: Operator Related Settings
214
YASKAWA ELECTRIC
SIEP C710606 44B YASKAWA AC Drive T1000V Technical Manual
Note: 1.
Parameter o1-03 allows the programmer to change the units used in the following parameters and monitors:
x
U1-01: frequency reference
x
U1-02: output frequency
x
U1-05: motor speed
x
U1-16: output frequency after softstarter (accel/decel ramp generator)
x
d1-01 to d1-17: frequency references
2.
Setting o1-03 to 2 requires that the number of motor poles be entered to E2-04, E4-04, and E5-04.
■
o1-10: User-Set Display Units Maximum Value
Determines the display value that is equal to the maximum output frequency. The decimal number is defined by
parameter o1-11.
Note:
This setting changes automatically when o1-03 is changed. o1-10 can only be adjusted when o1-03 is set to 3.
■
o1-11: User-Set Display Units Decimal Display
Determines the number of digits for user-set display if o1-03 is set to 3. The setting value is equal to the number of
decimal places. The maximum display value is defined by o1-10.
Note:
This setting changes automatically when o1-03 is changed. o1-11 can only be adjusted when o1-03 is set to 3.
◆
o2: Digital Operator Keypad Functions
These parameters determine the functions assigned to the operator keys.
■
o2-01: LO/RE (LOCAL/REMOTE) Key Function Selection
Parameter o2-01 determines whether the LO/RE key on the digital operator will be enabled or not for switching between
LOCAL and REMOTE.
Setting 0: Disabled
The LO/RE key is disabled.
Setting 1: Enabled
The LO/RE switches between LOCAL and REMOTE operation. Switching is possible during stop only. When LOCAL
is selected, the LED indicator on the LO/RE key will light up.
WARNING!
Sudden Movement Hazard. The drive may start unexpectedly if the Run command is already applied when switching from
LOCAL mode to REMOTE mode when b1-07 = 1, resulting in death or serious injury. Be sure all personnel are clear of rotating
machinery and electrical connections prior to switching between LOCAL mode and REMOTE mode.
■
o2-02: STOP Key Function Selection
Selects if the STOP key on the digital operator can be used to stop the operation when the drive is controlled from a
remote source (i.e., not from digital operator).
Setting 0: Disabled
The STOP key has no function when the drive is controlled by a source other than the digital operator. The drive can only
be stopped from the Run command source that has been selected.
No.
Name
Setting Range
Default
o1-10
User-Set Display Units Maximum Value
1 to 60000
Determined by
o1-03
No.
Name
Setting Range
Default
o1-11
User-Set Display Units Decimal Display
0 to 3
Determined by
o1-03
No.
Name
Setting Range
Default
o2-01
LO/RE Key Function Selection
0 or 1
1
No.
Name
Setting Range
Default
o2-02
STOP Key Function Selection
0 or 1
1