4.9 Verifying Parameter Settings and Backing Up Changes
YASKAWA ELECTRIC
SIEP C710606 44B YASKAWA AC Drive T1000V Technical Manual
97
S
ta
rt
-U
p Pr
og
ra
mmin
g
&
O
p
er
at
io
n
4
◆
Password Settings: A1-04, A1-05
The user can set a password to the drive to restrict access. The password is selected via parameter A1-05. The selected
password must be entered in parameter A1-04 to unlock parameter access (i.e., parameter setting A1-04 must match the
value programmed into A1-05). The following parameters cannot be viewed or edited until the value programmed into
A1-04 correctly matches the value as programmed in parameter A1-05: A1-01, A1-02, A1-03 and A2-01 through A2-33.
Note:
Parameter A1-05 is hidden from view. To display A1-05, access parameter A1-04 and simultaneously depress the
key and
the
key.
◆
Copy Function (Optional)
Parameter settings can be copied to another drive to simplify parameter restoration or multiple drive setup. The drive
supports the following options:
■
USB/Copy Unit (JVOP-181)
The copy unit is an external option connected to the drive to copy parameter settings to another drive. It includes a USB
adapter to connect the drive to a PC.
■
LCD Operator (JVOP-180)
The LCD operator supports copying, importing, and verifying parameter settings.
for details.
Note:
The LCD operator is available from software versions 6000 or later.
■
LED Operator (JVOP-182)
The LED also supports copying, importing, and verifying parameter settings.
Refer to o3: Copy Function on page 216
for details.
Note:
The LED operator is available from software versions 6000 or later.
■
Drive Wizard
Drive Wizard is a PC software tool for parameter management, monitoring, and diagnosis. Drive Wizard can load, store,
and copy drive parameter settings. For details, refer to Help in the Drive Wizard software.